I have not found a section 14a page for installers at Viessmann. The answer is in the installation and service instructions of the Vitocal 250-A: two contacts, one parameter for the consumption limit – and a heater that counts towards the minimum power and pushes the value up.
The installation and service instructions of the Vitocal 250-A (type 251.A, edition 4/2025) describe control by the grid operator via two digital inputs of the indoor unit, 143.4 and 143.5. For contact 143.4 alone they say: “The heat pump can be switched off by the utility or its power consumption can be limited. The power limitation is set during commissioning.” Each time, Viessmann adds: “(power limitation in accordance with section 14a EnWG)”.
With the second contact 143.5, power limitation can be combined with the utility lockout or with Smart Grid. What the heat pump does in which switching state is set out in a table in the instructions:
| Assignment | 143.4 | 143.5 | Operating state |
|---|---|---|---|
| Power limitation only | open | – | normal operation |
| Power limitation only | closed | – | power limitation active |
| Utility lockout and power limitation | open | open | normal operation |
| Utility lockout and power limitation | closed | open | power limitation active |
| Utility lockout and power limitation | closed | closed | utility lockout, heat pump off |
| Smart Grid and power limitation | open | open | normal operation (Smart Grid mode 2) |
| Smart Grid and power limitation | closed | open | power limitation active (Smart Grid mode 1) |
| Smart Grid and power limitation | open | closed | adjusted temperature setpoints (mode 3) |
| Smart Grid and power limitation | closed | closed | forced operation (mode 4) |
In the commissioning assistant this means setting “power limitation” to “potential-free contacts”, entering the value under “consumption limit setpoint” and, depending on the assignment, setting “Smart Grid” to “inactive”, “utility lockout” or “SG Ready via potential-free contacts”.
For the state “power limitation active”, the instructions list: “Limited electrical power consumption of the heat pump and the instantaneous heating water heater, possibly resulting in lower heat output”. Space heating and cooling then run via an external buffer tank, if present; an external heat generator supports if needed. This matches the Bundesnetzagentur's ruling: it treats the heat pump heating system “including supplementary or emergency heating devices (e.g. heating elements)” as one controllable consumption device (clause 2.4.1 b).
In the chapter on the mains connection, Viessmann writes: “Instead of a complete shutdown (utility lockout), the power of the heat pump is limited to a maximum of 4.2 kW. The calculated or specified power limitation for the installation is set during commissioning.” The operating instructions add that the exact value depends “on the electrical power consumption of your heat pump”. “To a maximum of 4.2 kW” refers to the lower limit: under direct control, the grid operator must allow at least 4.2 kW, and for heat pumps with a grid connection capacity above 11 kW the grid connection capacity times 0.4 (clause 4.5.1).
With the Vitocal 250-A this is not an edge case. The reasons for the ruling state: “When considering the power of heat pumps, supplementary or emergency heating devices (e.g. heating elements) are also to be included”. According to the technical data, the instantaneous heating water heater has up to 8 kW. Using the maximum values, the three-phase 251.A16 comes to 7.2 kW for the outdoor unit plus 8 kW, 15.2 kW in total. The minimum power would then be 0.4 × 15.2 kW = 6.08 kW. By this calculation, only the smallest single-phase size, 251.A04, stays below 11 kW with 2.3 + 8 = 10.3 kW.
Which grid connection capacity actually applies follows from the registration with the grid operator. Entering a flat 4.2 kW where more is due makes the heat pump throttle harder during curtailment than the ruling requires.
With the utility lockout alone, a closed contact at 143.4 means normal operation and an open one means lockout. With power limitation it is the other way round: open means normal operation, closed means limited. Anyone converting an installation from utility lockout to power limitation therefore changes not only the parameter but also checks which switching state the control box delivers during curtailment.
Two more points from the instructions belong to the wiring: the mains connection of the heat pump controller and “the cable for the utility signal (lockout or power limitation)” are routed separately to avoid malfunctions. And: “The power supply to the heat pump controller/electronics must not be subject to the utility lockout.” The controller therefore stays powered even during a lockout.
For the Vitocal 150-A and 250-A in the Modular, Compact and Hybrid variants, the operating instructions of July 2025 are publicly available. They describe the same principle: via two switching contacts, “the utility can lock the heat pump or limit its electrical power consumption in accordance with section 14a EnWG, depending on how your heat pump is connected and configured”. They do not name terminals or parameters; on the date of checking, the installation instructions were not available in the public area of Viessmann's document search ViBooks. For the hybrid units, Viessmann writes in its guide: “In the event of a lockout or throttling, the gas heating takes over heat generation.”
The guide on viessmann.de places the two-hour limit correctly in its summary: throttling “to at least 4.2 kW (preventively at the start, max. two hours a day)”. In the answers to frequently asked questions this restriction is missing: “The supplier may reduce the power of a heat pump to at least 4.2 kW for up to two hours a day.” Under the ruling, the limit of two hours a day applies only to preventive control, which the grid operator may use on a transitional basis until 31 December 2028 at the latest (clause 10.5). For grid-oriented control it sets no hour limit.
In the Viessmann documents analysed – installation and service instructions, both operating instructions and the current data sheets of the Vitocal 250-A – only the route via the contacts is described for control by the grid operator. Whether, and from which software version, a Vitocal accepts the control box's instruction digitally is not stated there. Only Viessmann can answer that for the specific unit, preferably in writing.
For section 14a, any route the manufacturer names is enough. For subsidising a newly installed heat pump it is not: under number 3.4.3, the BEG EM directive of 17 August 2026 requires a “digital interface for grid-oriented control” that is “interoperable” and enables control under section 14a “including the status and feedback information required for it”. A contact that opens or closes provides no feedback. From 1 July 2027, the interface of newly installed heat pumps must also follow a format in line with the Code of Conduct for Energy Smart Appliances, “for example EEBUS in accordance with VDE-AR-E 2829-6”.
Whether a specific installation is subsidised is decided by the funding body, not the manufacturer. The connection routes compared: Running a heat pump on electricity prices.
According to the installation and service instructions, via potential-free contact 143.4 of the indoor unit. If “power limitation” is set to “potential-free contacts” in the commissioning assistant, a closed contact limits the power consumption of the heat pump and the instantaneous heating water heater to the configured “consumption limit setpoint”. Via the second contact 143.5, this can be combined with the utility lockout or with Smart Grid.
The minimum power the grid operator must allow: 4.2 kW under direct control, and for a grid connection capacity above 11 kW the grid connection capacity times 0.4. Under the ruling, the instantaneous heating water heater of up to 8 kW counts as well. Using the maximum values from the technical data, almost all sizes of the Vitocal 250-A are therefore above 11 kW; the 251.A16 comes to 6.08 kW. Which grid connection capacity applies is stated in the registration with the grid operator.
Not unchanged. With the utility lockout alone, a closed contact at 143.4 means normal operation and an open one means lockout. With power limitation it is the other way round: the closed contact limits. Changing the function therefore reverses the contact logic, and the switching state of the control box during curtailment has to match it.
The manufacturer information comes exclusively from the manufacturer's own documents, each with its date and the date it was checked. Manufacturer documents change with every firmware release; what counts is the version valid at the time of installation. Quotations from German documents are our translation.
This article reproduces manufacturer information; it replaces neither Viessmann's documentation nor the technical connection conditions of your grid operator. Connection and registration are reserved for a registered electrical contractor. Haag Automation has no business relationship with Viessmann.