How many PV panels do you have? From that the configurator works out which charge
controllers, which MultiPlus and which battery fit – and compiles the parts list with Victron part
numbers, cables and the settings for commissioning. At Victron the information is spread out: one
compatibility page per battery manufacturer, plus the ESS manual, inverter manuals and datasheets.
Your parts list
What connects where
Parts for the Victron ESS, according to Victron's documentation.
Marked *: affiliate links. As an Amazon Associate I earn from qualifying purchases.
Part
Qty
Victron no.
Note
MPPT sizing
Settings during commissioning
Links marked with an asterisk in the parts list are affiliate links. As an
Amazon Associate I earn from qualifying purchases; the price is unchanged for you. What goes
into the list does not depend on it: there is only a link where the offer is exactly the
named part – as a checked product or as an Amazon search whose first result matches. The
Victron offers checked are sold by specialist dealers, not Victron itself.
Produces
proposal from number of panels and consumption, parts list and settings for a grid-parallel ESS with a 48 V MultiPlus-II
Batteries
24 manufacturers from AXIstorage to ZYC Energy
Panels
six series from AIKO to Trina, others with values entered by hand
Basis
Victron compatibility pages and the manufacturer documents linked there, ESS manual, MultiPlus-II manual and datasheet, panel datasheets, HTW Berlin's rules of thumb
Your data
stays in your browser, nothing is stored
As of
15 October 2026 · primary sources below, check date for each
At home I run a Pylontech US2000C on a Victron system. Finding the right parts was hard – not
because the information is missing, but because it sits in many places. The most important
piece depends on the battery: Victron makes the cable to the GX device in two pin-outs, and
with Pylontech the right one differs even within the same series.
How the proposal is made
The proposal answers four questions in turn. Each answer rests on a source listed below.
How many charge controllers? The configurator splits the panels across SmartSolar
controllers: as many in series as keeps the open-circuit voltage at the lowest temperature below
Victron's limit for start-up and operation while the voltage at 25 °C stays above the battery,
and as many strings in parallel as the short-circuit current allows. It looks for the split with
the fewest controllers; on a tie, identical controllers beat mixed ones, long strings beat short
ones and smaller controllers beat larger ones. Without power limiting the panel power per controller stays within its nominal power; with
“as few as possible” it may exceed it, and the controller then limits.
Which MultiPlus? The controllers' solar power has to pass through the MultiPlus into
the house and the grid. The proposal is the smallest setup whose continuous power at 25 °C
according to the datasheet reaches the controllers' power. A single unit only qualifies up to
4.6 kVA, the per-phase limit that the MultiPlus-II unit certificate also states: the 48/3000
with 2.43 kVA and the 48/5000 with 4.39 kVA. Above that it becomes three units, one per
phase. If the panels are on an existing inverter, the MultiPlus remains your choice.
How large the battery? According to HTW Berlin's rules of thumb: usable capacity at
most 1.5 kWh per kW of PV power and at most 1.5 kWh per 1,000 kWh of annual
consumption – the smaller value is the upper limit. According to HTW, a larger battery raises
self-sufficiency only slightly. Below 0.5 kW of PV power per 1,000 kWh of consumption there
is too little surplus for a battery.
Which battery? First, whether the battery stays below the upper limit with its
minimum number. Then how completely the connection is documented: whether Victron, or a manufacturer
document on Victron's page, states the minimum for exactly this MultiPlus, whether DVCC sets itself
and whether the cable is known. Only then does closeness to the upper limit decide, on a tie the
smaller number of modules. The best model per manufacturer is shown, four in total.
What the proposal does not know: prices, availability, your roof areas and how many battery modules
may work together at most. Parallel strings on one controller have the same length; that all panels
in a string should face the same way is something the configurator cannot check.
Panels in the selection, values at 25 °C according to the manufacturer datasheet, checked on 15 Oct 2026
Series
Power
Voc
Isc
Temperature coefficient Voc
Datasheet
AIKO Neostar 2P MAH54Mw
450–485 W
40.94–41.36 V
14.12–14.41 A
−0.22 %/K
V4.1_202510
JA Solar JAM54D40/MB
420–445 W
38.28–39.65 V
13.65–13.90 A
−0.25 %/K
Global-EN-20240729A
JA Solar JAM72D40/MB
580–605 W
51.95–53.00 V
13.84–14.09 A
−0.25 %/K
Global-EN-20241105A
Jinko Tiger Neo 3.0 48QL6-DB
460–485 W
35.69–36.94 V
15.70–15.94 A
−0.24 %/K
JKM460-485N-48QL6-DB-F4-EU
LONGi Hi-MO X10 LR7-54HVH
480–505 W
40.29–40.85 V
15.13–15.62 A
−0.20 %/K
BGV03 20260509
Trina Vertex S+ NEG9R.28
450–475 W
52.9–55.0 V
10.74–10.93 A
−0.24 %/K
TSM_EN_2026_A
The selection covers widely used series from large manufacturers whose datasheet the manufacturer
itself offers for download. If your panel is missing, choose “other panel” and enter the values
from its datasheet.
How the list is built
Every line comes from a Victron source or from a manufacturer document that Victron links on its
compatibility page; which one is listed below. Three things decide whether
the system starts up, and all three depend on the battery:
The cable between battery and GX device. Mostly Victron makes it in two
pin-outs, type A and type B; they differ in the ground pin on the battery side.
Some batteries take a standard network cable or come with their own. Without the
right connection the battery does not appear on the GX device, and Pylontech and BYD then
switch themselves off.
The minimum number of modules. The battery has to carry the inverter's
start-up inrush current and the load. Victron gives the figures for only some of the
batteries, some manufacturers in their own documents on the Victron pages; where both are
missing, the configurator says so instead of guessing.
Firmware and DVCC. Every battery requires a minimum version on the GX
device. With Pylontech the GX device sets the DVCC values itself, with Dyness you set them
by hand.
BMS cable, minimum GX firmware and DVCC per battery, according to Victron, checked on 14 Oct 2026; information from manufacturer documents on the Victron pages in brackets, checked on 15 Oct 2026
Victron now lists new part numbers for both cables: type A ASS030710118, type B
ASS030720118, each 1.8 m; the 5 m versions end in …150. The battery pages still
give the old numbers ending in …018; the product page points to the new ones.
The GX device decides how many CAN connections stay free. Cerbo GX MK2, Cerbo GX MK3 and Ekrano GX have two:
one for the battery, one for VE.Can devices. The Cerbo-S GX has only one, and the built-in GX
of the MultiPlus-II GX has a dedicated BMS-Can port on which VE.Can devices do not work. An
MPPT solar charger then connects via VE.Direct.
How the MPPT sizing works
For panels on the Victron the configurator uses the values from the panel datasheet; they apply at
25 °C cell temperature (standard test conditions). Every controller with its parallel strings
has to meet the limits in Victron's datasheets:
Open-circuit voltage in the cold: panels in series × Voc × (1 + temperature
coefficient × (lowest temperature − 25 °C)). It must not exceed the absolute maximum,
150 V for the 150 models, 250 V for the 250 models. For start-up and operation
Victron gives 145 and 245 V.
Short-circuit current: strings in parallel × Isc. According to the datasheet,
an array with a higher short-circuit current may damage the controller.
Start voltage: the PV voltage must exceed the battery voltage by 5 V for
the controller to start, thereafter by 1 V. The check uses the higher of the battery's
charge voltage and 57.6 V, the absorption voltage from the MultiPlus-II datasheet.
Power: if more panel power is connected than the nominal power at
48 V, the controller limits input power. Without power limiting the configurator does not
allow this.
SmartSolar controllers in the selection, values according to the Victron datasheet, checked on 14 Oct 2026
Controller
Nominal power at 48 V
Max. short-circuit current
Max. open-circuit voltage (start/operation)
SmartSolar MPPT 150/35
2,000 W
40 A
150 V (145 V)
SmartSolar MPPT 150/45
2,600 W
50 A
150 V (145 V)
SmartSolar MPPT 150/60-Tr
3,440 W
50 A
150 V (145 V)
SmartSolar MPPT 150/70-Tr
4,000 W
50 A
150 V (145 V)
SmartSolar MPPT 250/60-Tr
3,440 W
35 A
250 V (245 V)
SmartSolar MPPT 250/70-Tr
4,000 W
35 A
250 V (245 V)
In the heat the panel voltage drops below the 25 °C value. By how much is given as the
temperature coefficient in the panel datasheet; the configurator does not calculate this case. It
therefore prefers long strings – allow a margin between MPP voltage and battery voltage.
More controllers than the GX device has VE.Direct ports connect to a USB port via the VE.Direct to
USB interface (ASS030530010). According to the GX manual, the Cerbo GX MK2 handles up to 15
VE.Direct devices, the MK3 up to 25.
Registration and connection
A MultiPlus-II in ESS mode works in parallel with the grid. For registration with the German
grid operator, Victron provides the unit certificate and the certificate for the grid and
system protection (NA-Schutz) to VDE-AR-N 4105:2018-11 – for the 3, 4.5, 5 and
6.5 kVA models (also as GX) and for 8, 10 and 15 kVA, there additionally in
three-phase configuration. They are on the
product pages
under Downloads.
Registration needs a single-line diagram. What it has to show is covered in the article
PV single-line diagram, which also has
sample sheets with storage. If you would rather not draw it yourself:
I draw it for €50. Within one month
of commissioning, the battery goes into the
Marktstammdatenregister.
Connecting to 230/400 V is reserved for a qualified electrician. The parts
list does not replace planning the AC side: circuit protection, residual current protection
and the meter panel are decided there.
What the configurator does not cover
Off-grid systems and backup power. It plans a grid-parallel ESS. If you
want supply to continue during a grid outage, plan the AC output and the changeover with
the electrician; for off-grid systems the manufacturers give higher minimum numbers.
Quattro, Multi RS and MultiPlus-II 4k5 and 6k5. The battery manufacturers'
tables only partly cover them.
MPPTs above 70 A and MPPT RS. For the 85 and 100 A controllers Victron's
datasheet links currently redirect to the 60/70 A version; without their own limits they are
not in the selection. For larger arrays there is Victron's
MPPT calculator.
DC distribution with Lynx or busbars, and more than one battery bank.
Prices, availability and roof areas. The proposal works with datasheets, not
with quotes. How the panels face and how many battery modules may work together at most is a
matter for your planning and the battery manual.
Self-built batteries. Victron names four BMSes that implement the interface
correctly (123\SmartBMS, Batrium, Boostech, REC), but does not test them and offers only
very limited support for such systems.
Five entries from Victron's list. Victron lists 29 tested battery systems, the
configurator contains 24. Not included: BattleBorn and SimpliPhi do not communicate with the GX
device, for Rolls Victron only links a manufacturer document, MG Energy Systems connects to the
VE.Can port with its own instructions, and for Victron's own lithium batteries the list links
their product page. For Discover the AES RACKMOUNT range on the LYNK II gateway is missing.
Frequently asked questions
How large should the battery be for my PV system?
According to HTW Berlin's rules of thumb, at most 1.5 kWh of usable capacity per kW of PV power and
at most 1.5 kWh per 1,000 kWh of annual consumption; the smaller value applies. With 10 kW of PV
power and 4,000 kWh of consumption that is 6 kWh. A larger battery raises self-sufficiency only
slightly, and below 0.5 kW of PV power per 1,000 kWh of consumption there is too little surplus for
a battery, according to HTW. With Victron there is one more point: the battery has to carry the
MultiPlus, and some manufacturers require more modules for that than the rule of thumb gives.
Which cable connects the battery to the Victron GX device?
Usually Victron's VE.Can to CAN-bus BMS cable, in type A or type B; which one depends on the
battery model, with Pylontech even on the design within the same series. Cegasa, Bluenova and
Freedom Won LiTE use a standard network cable instead; Exide and the Freedom Won eTower come
with their own cable. The table further up lists the mapping for all 24 manufacturers. The
cable Pylontech supplies does not fit the connection to the GX device.
Do I need a grid meter?
Yes, as soon as loads or a PV inverter sit between the grid connection and the Victron – the
usual case, where the house wiring stays as it is. Without a meter, the GX device then works
with wrong grid and consumption figures. Only if everything is on the MultiPlus AC output can
you do without. Single-phase, that is the ET112; on a three-phase connection Victron
recommends the EM24 rather than the ET340, because it counts the net sum.
Are my entries stored?
No. Proposal and parts list are built in your browser. Number of panels, consumption, your selection
and panel data only appear in the part of the address after the #, which the browser does not send
to the server; Google Analytics receives the address without that part. All that is recorded is that
a parts list was created or copied, plus battery manufacturer, layout and type of GX device.
Sources
The information comes from Victron Energy's documentation, from the manufacturer documents Victron
links on its compatibility pages, from the panel manufacturers' datasheets and from HTW Berlin. If in doubt, the current version at
the manufacturer and the battery manual take precedence.
OverviewVictron – Battery Compatibility29 tested battery systems; usually connected via BMS-Can on a GX device; four self-build BMSes that follow the specification but are not tested, with very limited support. Checked on 14 Oct 2026.
Storage sizeHTW Berlin – Empfehlungen zur Auslegung von SolarstromspeichernOrth, Weniger, Meissner, Sonnenenergie 02/2022 (German). Three rules of thumb: PV power at least 0.5 kW per 1,000 kWh/a, usable storage capacity at most 1.5 kWh per kW of PV power and at most 1.5 kWh per 1,000 kWh/a; example 10 kW and 4,000 kWh/a → at most 6 kWh. Checked on 15 Oct 2026.
MultiPlus-IIMultiPlus-II 230 V datasheet ·
Unit certificate 19-117-04 ·
Unit certificate 8, 10 and 15 kVADatasheet: continuous power at 25 °C 2,400, 4,000, 6,400, 8,000 and 12,000 W (48/3000 to 48/15000), absorption voltage 57.6 V. Certificate 19-117-04 (Kiwa, 1 Oct 2025): max. apparent power 2.43 kVA (48/3000) and 4.39 kVA (48/5000); several single-phase units evenly across all phases, otherwise at most 13.8 kVA, max. 4.6 kVA per phase. Certificate 2622/0478-A-1-E3-CER (SGS, 11 Jun 2026): 8, 10 and 15 kVA single-phase. Checked on 15 Oct 2026.
Feed-in limit§ 9 EEG 2023 – technical requirements (German)Para. 2 sentence 1 no. 3: systems below 25 kW receiving the feed-in tariff limit active power feed-in at the grid connection point to 60 percent of installed capacity. Checked on 15 Oct 2026.
PylontechVictron & PylontechGX from v3.50, VE.Bus from 469, MPPT from 1.37; type A for US2000C/D, US3000C, UP5000, US5000(B), Force-L, type B for US2000, US3000, UP2500; Pylontech's supplied cable unsuitable; minimum number as an example for the US2000 (2, 4, 6, 7, 10 modules); DIP switches 000; DVCC automatic on the BMS-Can port from v2.80; values for VEConfigure and the ESS assistant. Checked on 14 Oct 2026.
BYDVictron & BYDMinimum number tables per model (columns On-Grid or Self-consumption); GX from v2.52 (Premium LV) or v3.20 (LV5.0+); battery from V1.4, BMS from V1.3 (Premium) or 1.2 (LV5.0+); type A; DVCC on, SVS off; values for VEConfigure and the ESS assistant; HVS/HVM not compatible. Checked on 14 Oct 2026.
DynessVictron Energy & Dyness BatteriesModel list; GX from v3.31, VE.Bus from 469; type A to CAN IN or EXT CAN, not type B and no network cable; terminator in the BMS-Can port; DVCC by hand; ESS option “System uses LiFePO4 with other type BMS”; minimum number from the supplier. Checked on 14 Oct 2026.
BSLBATTVictron & BSLBATT Lithium batteriesType B; GX from v2.52, VE.Bus from 469; minimum number for 5.1, 6.4, 8.2 and 10.2 kWh; values for VEConfigure and the ESS assistant; always terminate the CAN port on the GX; plus seven BSLBATT guides v1.3, see manufacturer documents. Checked on 14 Oct 2026.
BMZVictron & BMZESS 7.0, 9.0, X, Z with capacity in Ah; type B; only with the ESS assistant; the fourth battery option according to the text, the image shows “System uses LiFePO4 with other type BMS”; charge values; DVCC table as an image (SVS and STS off for BMZ, BYD and Pylontech, SVS on for Freedom Won); external supply for the GX at first commissioning. The page still mentions CCGX and Venus GX. Checked on 14 Oct 2026.
Pytes, WeCoVictron & Pytes ·
Victron & WeCoBoth GX from v3.31, VE.Bus from 469, BMS-Can or VE.Can; Pytes type A, firmware from 1.10.18, DVCC on, SVS and STS off; WeCo: DVCC and SVS forced on, STS off, cable type not given. Minimum number from the supplier in both cases. Checked on 14 Oct 2026.
Further manufacturersAXIstorage ·
Bluenova ·
Cegasa ·
Discover ·
Exide ·
Freedom Won ·
Hubble ·
LBSA ·
Leoch ·
MeterBoost ·
SolarMD ·
Soluna ·
StorageDOCK ·
Sunwoda ·
TAB ·
Voltsmile ·
ZYC EnergyCable type, minimum firmware, DVCC, values for VEConfigure and the ESS assistant, minimum number and connection, where the pages state them. Not included: BattleBorn and SimpliPhi (no communication with the GX), Rolls (manufacturer document only), MG Energy Systems (VE.Can with its own instructions), Victron Lithium (link to the product page) and Discover AES RACKMOUNT (LYNK II gateway). Read from images on the pages on 15 Oct 2026: ESS battery option “System uses LiFePO4 with other type BMS” (where the text says “externally managed Lithium battery option”), minimum number Leoch LR51.2-100, dynamic cut-off Freedom Won, charge values and DVCC Bluenova. Checked on 14 Oct 2026.
Manufacturer documentsLBSA ·
BSLBATT 5.1 kWh ·
Leoch ·
Sunwoda ·
Pytes 51.2 V ·
Pytes 48 V ·
Pytes battery brief ·
MeterBoost ·
TAB ·
ZYCPDFs that Victron links on the compatibility pages. LBSA: values for VEConfigure and the ESS assistant, DVCC, sizing by continuous power (5000 VA → at least 5 kWh). BSLBATT, guides v1.3 for 5.1, 6.4, 7, 8.2/8.8, 10.2 and 15 kWh and Powerline-5: minimum number per model (single-phase only), ESS option, DVCC with SVS. Leoch: values for VEConfigure and ESS, DVCC, type A or B. Sunwoda and Pytes: values for VEConfigure and ESS, for Pytes from the image labels, models according to the battery brief. MeterBoost, rev. 2024-3: values from the screenshots, terminator at the GX, DVCC and SVS forced on. TAB: 120 Ω termination, DIP switch 4. ZYC: type A, terminating resistor at the last battery. Checked on 15 Oct 2026.
BMS cableVE.Can to CAN-bus BMS cables manual ·
product pageMapping to the batteries, pin-out (ground on pin 6 for type A, pin 2 for type B); part numbers ASS030710118/…150 and ASS030720118/…150 replacing …018 and …050. Checked on 14 Oct 2026.
GX devicesVictron – GX product overview ·
Cerbo GXCerbo-S GX without BMS-Can port; Cerbo GX MK2 and Ekrano GX with two CAN connections; BMS-Can fixed at 500 kbit/s, no VE.Can devices; original Cerbo GX discontinued; two VE.Can terminators supplied with the GX device according to the battery pages. Checked on 14 Oct 2026.
GX manualEkrano GX, Cerbo GX, Nucleo GX Manual, Rev 42 – 10/2026Cerbo GX MK2 and MK3 each with two VE.Can (VE.Can 1 isolated), three VE.Direct ports, VE.Bus, USB and Ethernet; MK3 up to 25 VE.Direct devices, MK2 up to 15 (chapters 3.1 and 22). Checked on 14 Oct 2026.
ESS manualESS design and installation manual, Rev 11 – 10/2024Hardware list in chapter 9.3 (MK3, GX device, RJ45 cables, meters, RS485 to USB, VE.Direct); grid meter only dispensable without loads and PV ahead of the AC input; single-phase ESS on a three-phase connection on L1; multiphase regulation; three-phase ESS with at least three units; EM24 rather than ET340; PV measurement without extra hardware only for Fronius, SMA, ABB and SolarEdge. Checked on 14 Oct 2026.
Inverter manualsMultiPlus-II 230V, Rev 14 – 07/2026 ·
MultiPlus-II GX, Rev 13 – 07/2026DC fuse and cross-section per model (table in chapter 4.3); parallel and three-phase operation only with identical units on the same battery, DC cables of equal length and cross-section, UTP cables direct (chapters 4.5.7 and 4.5.8); on the GX model a dedicated BMS-Can port and, for three-phase systems, the recommendation to use units without GX plus an external GX device. Checked on 14 Oct 2026.
MPPTDatasheet 150/35 & 150/45 ·
150/60 & 150/70 ·
250/60 & 250/70 ·
product pageNominal power at 48 V, maximum PV short-circuit current, maximum open-circuit voltage absolute and for start-up and operation; footnotes: start from battery voltage + 5 V, thereafter + 1 V, more panel power is limited, a higher short-circuit current may damage the controller. Part numbers of the Tr versions from the product pages. The datasheet links of the 85 and 100 A controllers currently redirect to the 60/70 A version. Checked on 14 Oct 2026.
Product pagesMultiPlus-II ·
MultiPlus-II GX ·
Energy Meters ·
MK3-USB-C ·
RS485 to USB ·
VE.Can terminator ·
VE.Direct to USBPart numbers of the units; VE.Direct to USB interface ASS030530010 (checked on 15 Oct 2026); certificates to VDE-AR-N 4105:2018-11 (unit certificate and NA protection); ET112 single-phase up to 100 A, EM24 Ethernet and EM540 three-phase up to 65 A per phase, EM540 as successor of the EM24 with RS485, VM-3P75CT with current transformers, 75 A rated current, Ethernet and VE.Can. Checked on 14 Oct 2026.
Planning a Victron system and want to control it with Home Assistant afterwards?
Write to me – the first conversation is free.