Stiebel Eltron states that all of its heat pumps installed today comply with section 14a. What that looks like technically is not on the advice page but in the instructions of the Internet Service Gateway ISG Connect: two routes, four input modes and four places where the control box signal can arrive. On top of that, two statements on the manufacturer's website that only hold for part of the installations.

Basis
operation and installation ISG Connect, 361535-47110-0040, edition April 2025 (German)
Routes
switch-off via utility contact · power limitation via ISG Connect
Inputs
WPM, ISG Connect, KNX or Modbus, two bits each
EEBUS
not described in the instructions
Status
October 2026 · primary sources below, with the date each was checked
Author
Julian Haag, state-certified electrical engineering technician

What Stiebel Eltron promises

On its advice page on controllable consumption devices, Stiebel Eltron writes that all Stiebel Eltron heat pumps installed today comply with section 14a of the Energy Industry Act. In combination with the ISG Connect, the heat pumps do “not switch off completely but temporarily reduce their output” when the grid operator sends a signal. The same wording appears in the ISG Connect instructions, with the note that this control meets the requirements of section 14a EnWG.

The condition is in the subordinate clause: dimming instead of switching off runs via the ISG Connect, an accessory with part number 206780. Without the ISG, according to the instructions, the utility contact remains, and it only knows on and off.

The two routes according to the instructions

Section 7.7 of the instructions names two ways of controlling the heat pump's output:

  1. Switch-off via the utility contact of the heat pump manager (WPM). Contact open: the heat pump is switched off, only frost protection stays active. Contact closed: normal operation. For the exact terminal assignment the instructions refer to the instructions of the respective heat pump.
  2. Control via the ISG Connect. In translation: “From WPM firmware 14, LWZ and ISG Connect firmware 1.4.0, the heat pump's output can be reduced without a full switch-off.” Before setting it up, the contractor should check the software versions on the WPM under Diagnose › System › Busteilnehmer.

Which devices work with the ISG Connect at all is governed by a separate compatibility list. The instructions name the production date and the minimum software of the WPM as prerequisites.

Where the control box signal arrives

The ISG Connect evaluates two inputs, input 1 and input 2. Where the two bits come from is set by the contractor as the “input source”. The instructions name four:

Input sources for power control of the ISG Connect
SourceInput 1Input 2Applies to
WPM, SG Ready inputX1.13 – 1X1.13 – 3WPMsystem
ISG Connect, SG Ready cableyellowgreenLWZ, WPM 3i
KNXobject 161object 162network control
Modbus IPregister 44002register 44003network control

For the two contact variants the instructions require two potential-free signal relays that bridge the signal inputs to GND. A control box with a relay output therefore fits directly on the WPM or on the ISG's SG Ready cable.

Stiebel Eltron: from the control box signal to the throttled heat pump At the top the grid operator's control box with a relay output. Below, four possible input sources for two bits: the SG Ready input on the WPMsystem with X1.13 terminals 1 and 3, the SG Ready cable on the ISG Connect with yellow and green for LWZ and WPM 3i, KNX with objects 161 and 162, and Modbus IP with registers 44002 and 44003. All lead to the ISG Connect from firmware 1.4.0 with input mode PL/LU or PL/FS and the power limit set there. At the bottom the heat pump, which keeps running within the limit or switches off if its minimum power is undercut. Control box (relay) Input source, input 1 / 2 each WPM X1.13 – 1 / – 3 ISG SG Ready cable yellow / green KNX object 161 / 162 Modbus IP register 44002 / 44003 ISG Connect from firmware 1.4.0 mode PL/LU or PL/FS · set the limit Heat pump: within the limit or off
Based on the ISG Connect instructions, 361535-47110-0040, section 7.7. Which source applies depends on the heat pump manager; the terminal assignment of the utility contact is in the heat pump's instructions.

The four input modes

How the two bits act is decided by the “input mode” in the SERVICEWELT under Einstellungen › Leistungsbeeinflussung. According to the instructions, individual modes may be missing depending on the heat pump.

Input modes of the ISG Connect (notation: input 1 – input 2)
Mode0 – 01 – 00 – 11 – 1
OFFoutput is not influenced
SG Readystandard operationstart recommendationswitch-off, frost protection onlymaximum operation
PL/LU (Power Limitation / Load Up)standard operationpower limitationstart recommendation (heat storage)power limitation
PL/FS (Power Limitation / Full Shed)standard operationpower limitationswitch-off, frost protection onlyswitch-off, frost protection only

The two PL modes are meant for section 14a. In both, the contractor configures the desired limit for a signal from the grid operator or control box. The difference is the second input: with PL/LU it serves as a start signal for heat storage, for example with PV surplus; with PL/FS it switches the heat pump off.

Under power limitation, according to the instructions, the heat pump operates within the limit or switches off if its minimum power is undercut; with a limit of 0 it is always off. That matches the Federal Network Agency's ruling: if a device cannot meet the specified value, it has to go to the next lower technically possible value (clause 4.6).

Two statements on the manufacturer's website, checked

Stiebel Eltron writes on its advice page that in case of an intervention by the grid operator a guaranteed lower power limit of 4.2 kW remains available. That holds for heat pumps up to 11 kW grid connection capacity. Above that, the minimum under direct control is the grid connection capacity times 0.4 (clause 4.5.1 of ruling BK6-22-300), i.e. more than 4.2 kW. How these limits come about is explained in The 4.2 kW in section 14a EnWG.

On duration, Stiebel Eltron writes that precautionary control by the grid operator, as a transitional solution, is limited to a maximum of two hours per day. That matches the ruling: preventive control is a transitional rule until 31 December 2028 at the latest, and its use is limited to two hours a day (clause 10.5). For grid-oriented control, the normal case afterwards, the ruling sets no limit in hours.

And EEBUS?

The ISG Connect instructions of April 2025 describe two bits for power control, arriving via relay, KNX or Modbus. EEBUS does not appear in them, nor in the older edition of April 2024. Other manufacturers in this series, such as Bosch, Buderus, Daikin and Vaillant, describe EEBUS for their heat pumps.

For section 14a itself that is not a shortcoming: the ruling allows control via a relay. For subsidies it can become one, see below. Anyone planning a Stiebel Eltron heat pump with BEG funding should ask the manufacturer in writing whether, and from which software version, a digital interface with feedback is available.

What the subsidy requires

For section 14a, any route the manufacturer names is enough. For subsidising a newly installed heat pump it is not: under number 3.4.3, the BEG EM directive of 17 August 2026 requires a “digital interface for grid-oriented control” that is “interoperable” and enables control under section 14a “including the status and feedback information required for it”. A contact that opens or closes provides no feedback. From 1 July 2027, the interface of newly installed heat pumps must also follow a format in line with the Code of Conduct for Energy Smart Appliances, “for example EEBUS in accordance with VDE-AR-E 2829-6”.

Whether a specific installation is subsidised is decided by the funding body, not the manufacturer. What applies if no control box is installed yet at the time of the application: KfW heat pump subsidy when the control box is still missing.

Frequently asked questions

How does a Stiebel Eltron heat pump meet section 14a EnWG?

Stiebel Eltron names two routes: switch-off via the utility contact of the heat pump manager and power reduction via the ISG Connect. According to the instructions, power reduction without a full switch-off requires “WPM firmware 14, LWZ and ISG Connect firmware 1.4.0”. The control box signal arrives on two inputs, either on the WPM, on the ISG Connect, via KNX or via Modbus.

Does Stiebel Eltron support EEBUS for section 14a?

The ISG Connect instructions of April 2025 describe two inputs for power control, switched via relay, KNX or Modbus. They do not mention EEBUS. Anyone installing a heat pump with BEG funding should ask the manufacturer in writing whether, and from which software version, a digital interface with feedback is available.

Does a Stiebel Eltron heat pump always keep 4.2 kW?

For heat pumps up to 11 kW grid connection capacity, yes; the Federal Network Agency's ruling requires it. Above that, under direct control the minimum is the grid connection capacity times 0.4. The manufacturer's website states a flat 4.2 kW. How much the heat pump actually gets also depends on the limit set in the ISG Connect.

What happens if the limit is below the heat pump's minimum power?

Then the heat pump switches off, according to the ISG Connect instructions. In the PL/LU and PL/FS modes it operates within the power limit or switches off if the heat pump's minimum power is undercut; with a limit of 0 it is always off. That matches the ruling: if a device cannot meet the value, it has to go to the next lower technically possible value.

Sources

The manufacturer information comes exclusively from the manufacturer's own documents, each with its edition and the date it was checked. Manufacturer documents change with every firmware release; the edition valid at the time of installation is what counts.

This article reproduces manufacturer information; it replaces neither Stiebel Eltron's documentation nor the technical connection conditions of your grid operator. Connection and registration are reserved for a registered electrical contractor. Haag Automation has no business relationship with Stiebel Eltron.