Article · Metering · Shelly

Shelly Pro 3EM, 3EM-63 or Pro EM-50: which one fits?

Seven Shelly energy meters are candidates for the house connection or individual circuits. They differ in measuring range, in the type of current transformer and in where they sit: as a separate device on the DIN rail or directly on a circuit breaker. On top of that, the best known of them, the Pro 3EM, has been superseded by a second version. This page arranges the data sheets so that the choice starts with the question of which connection is being measured.

Compared
Pro 3EM v2, Pro 3EM-3CT63, Pro 3EM-400, 3EM-63 Gen3, Pro EM-50, EM Gen3, 3EM
Basis
data sheets in the Shelly Knowledge Base and the Shelly shop
Status
checked on 13 October 2026 · sources below
Author
Julian Haag, state-certified electrical engineering technician

The key points in one minute

The devices at a glance

Shelly energy meters according to the data sheet, as of 13 October 2026
DeviceMeasurementCurrent transformersMountingNetwork
Pro 3EM v23 phases, 0–120 A3 CTs 120 ADIN rail, 19 mm wideLAN, Wi-Fi, Bluetooth
Pro 3EM-3CT633 phases, 0–63 A1 combined CT, openings Ø 9 mmDIN rail, 19 mm; CT freestanding on the conductorsLAN, Wi-Fi, Bluetooth
Pro 3EM-4003 phases, 0–400 ACTs 400 ADIN rail, 19 mmLAN, Wi-Fi
3EM-63 Gen3 (W, T)3 phases or 3 circuits, 0–63 Ain the housing, openings Ø 8 mmabove (W only) or below the circuit breakerWi-Fi, Bluetooth
Pro EM-501 phase, 2 channels, 0–50 A2 CTs up to 50 ADIN rail, 19 mmLAN, Wi-Fi
EM Gen31 phase, 2 channelsCT 50 A, optionally 80 Ahousing 37 × 42 mm, in the electrical cabinetWi-Fi
3EM (1st generation)3 channels3 CTs 120 Ahousing 73 × 57 mmWi-Fi

Two figures are missing from the table because they rarely decide, but sometimes surprise: how long the device stores readings itself when the connection is gone (Pro 3EM v2 at least 45 days, 3CT63, 400 and Pro EM-50 at least 60 days, EM Gen3 at least 10, 3EM-63 Gen3 at least 7 days), and whether a relay for a contactor is built in. The Pro EM-50, the EM Gen3 and the old 3EM have one. The Pro 3EM devices need an add-on for this.

Pro 3EM and Pro 3EM v2

Shelly lists the previous Pro 3EM 120A in its shop as discontinued: it is “no longer manufactured or sold”. As the direct successor Shelly names the Pro 3EM v2, which “enables a Matter upgrade”, available after updating to the latest firmware. Measuring range and connection stay the same: up to 120 A per phase and on the neutral. The data sheet in the Knowledge Base that both shop pages refer to describes a device with the identifier SPEM-003CEBEU, “Matter-ready”, with at least 45 days of data storage.

For Home Assistant the version makes no difference; both run via the Shelly integration. For a plug-in battery it can, more on that below.

Which measuring range for which connection

Measurement takes place where all the current of the house flows: behind the electricity meter, on all three line conductors. What matters is therefore the largest current that can flow there, and that is limited by the protection upstream. Above its measuring range, a device no longer measures correctly.

The Pro devices need upstream protection for their own power supply with characteristic B or C and at most 16 A. How much space this takes in the distribution board and how to choose the metering point is covered in the article Energy metering in the distribution board. If a channel shows negative values after installation where there should be import, the current transformer is usually the wrong way round; Shelly gives the direction as K → L.

A Shelly for a plug-in battery

Anyone buying the Shelly mainly so that a plug-in battery aligns its output with consumption should not choose by data sheet, but by the battery manufacturer's list. Anker, Marstek, EcoFlow and Zendure name the Pro 3EM, Anker and Zendure also the old 3EM. None of them names the 63 A devices. The table per battery model is in the article Smart meter for a plug-in battery.

With the Pro 3EM, the version is the open question. For the STREAM Ultra, EcoFlow names two article numbers, SPEM-003CEBEU120 and SPEM-003CEBEU; the second is the identifier in the current data sheet. Anker, Marstek and Zendure only write “Shelly Pro 3EM”. Whether their apps already recognise the v2 is not stated in the lists. Because Shelly no longer sells the old version, a short query to the battery manufacturer before buying is worthwhile.

In Home Assistant

All seven devices run via the Shelly integration, which is part of Home Assistant. It talks directly to the device; according to the documentation, no cloud connection is needed. On the old 3EM, a first-generation device, CoIoT must be enabled in the Shelly's web interface for this; the documentation recommends unicast with the address of the Home Assistant server.

For the energy dashboard one point matters more than the choice of device: the electricity meter sums across all three line conductors, the Shelly's energy counters per phase do not. How to build counters from this that count like the electricity meter is covered in the article Energy dashboard with the Shelly Pro 3EM.

Which Shelly for which job

Read on: where the meter sits in the distribution board, how much space it needs and how to check the measurement against the electricity meter is covered in the main article Energy metering in the distribution board.

Frequently asked questions

What is the difference between the Shelly Pro 3EM and the Shelly 3EM-63 Gen3?

The Pro 3EM is a separate device on the DIN rail, measures with three current transformers up to 120 A per phase and has LAN, Wi-Fi and Bluetooth. The 3EM-63 Gen3 has the current transformers in its housing, is mounted directly above or below a circuit breaker, measures up to 63 A and has only Wi-Fi and Bluetooth. It stores readings for at least 7 days, the Pro 3EM for at least 45 days.

What is the Shelly Pro 3EM v2?

The successor to the Pro 3EM 120A, which Shelly lists as discontinued. It also measures up to 120 A per phase and on the neutral and can be enabled for Matter after a firmware update. Anyone buying it for a plug-in battery should check the battery manufacturer's list: EcoFlow names two article numbers of the Pro 3EM, Anker, Marstek and Zendure only “Shelly Pro 3EM” without a version.

Which Shelly fits if the connection is protected at more than 63 A?

The Pro 3EM with 120 A current transformers, for even larger connections the Pro 3EM-400. The Pro 3EM-3CT63 and the 3EM-63 Gen3 only measure up to 63 A; according to Shelly, the 3EM-63 also requires protection of no more than 63 A.

Do I need an electrician for the Shelly Pro 3EM?

Yes. The Pro 3EM is connected to all three line conductors in the meter cabinet or sub-distribution board, and the current transformers go around the conductors behind the meter. That is work on 230/400 V and belongs in the hands of a qualified electrician. For the power supply, Shelly requires upstream protection with characteristic B or C and at most 16 A.

Sources

The technical information comes from the data sheets in the Shelly Knowledge Base, the information on the version from the Shelly shop. I have no measurements of my own with all seven devices; this page is a sourced comparison, not a test. What is written here applies as of 13 October 2026.

Haag Automation has no business relationship with Shelly. Work in the distribution board and the meter cabinet is reserved for a qualified electrician.

Links marked with an asterisk are affiliate links. As an Amazon Associate I earn from qualifying purchases; the price is unchanged for you. What I recommend does not depend on it.

Want to meter the house connection and have the readings properly in the energy dashboard? I can set it up with you – the first conversation is free.