Technical article · Home Assistant · Energy

The Home Assistant Energy dashboard with the Shelly Pro 3EM

Adding the Shelly Pro 3EM to Home Assistant takes minutes. Whether the numbers are right afterwards is decided in three places: which sensors end up in the Energy dashboard, whether the current transformers are fitted the right way round, and whether the Shelly counts the way the utility meter does. On the last point it does not, as soon as a PV system feeds in within the house. This page shows the setup and the correction.

Device
Shelly Pro 3EM, transformers up to 120 A per phase; variants with 63 A and 400 A
Connection
Shelly integration, local, values pushed
Into the dashboard
energy imported, energy returned, total power
Pitfall
energy counters per phase instead of netted as on the utility meter
Status
October 2026 · primary sources below, with the date each was checked
Author
Julian Haag, state-certified electrical engineering technician

The essentials in one minute

What the Energy dashboard needs

The Energy dashboard sorts everything into consumption, production and storage. For electricity there are sources for the grid connection, the solar system, the home battery and individual devices. Each source is a sensor with fixed properties, and only sensors that have them appear in the selection at all:

Which sensors the Energy dashboard accepts
Quantitydevice_classstate_class
Energy (kWh)energytotal or total_increasing
Power (W)powermeasurement
Battery state of charge (%)batterymeasurement

Power sensors can be configured alongside energy sensors. With them the dashboard shows not only what flowed in a period but also what is flowing right now. Everything is read from long-term statistics only: what the recorder does not record cannot be selected. How these statistics are created and what they keep is covered in Long-term data in Home Assistant.

Adding the Pro 3EM

The Pro 3EM sits in the meter cabinet or in a sub-distribution board downstream of the meter and measures via three current transformers placed around the phase conductors. That is work for an electrician; space, transformer measurement and the choice of measuring point are covered in Energy metering in the distribution board.

The three variants according to Shelly
VariantRange per phaseTransformers
Pro 3EM0 to 120 A, ±1 % from 2 to 120 Athree individual 120 A transformers
Pro 3EM-3CT630 to 63 A, ±1 % from 2 to 63 Acombined three-phase transformer, mounted over a circuit breaker
Pro 3EM-4000 to 400 A, ±1 % from 5 to 400 Athree 400 A transformers

Which variant fits depends on the current that can flow at the measuring point; above its range the device no longer measures. All three store measurement data even without a network connection, the Pro 3EM for at least 45 days according to Shelly. Which version fits which connection, also compared with the 3EM-63 Gen3 and the Pro EM-50, is covered in the article Shelly Pro 3EM, 3EM-63 or Pro EM-50: which one fits?

In Home Assistant

Home Assistant classifies the Shelly integration as “Local Push”: it talks to the device on the local network, and the device reports changes by itself. For devices from the second generation onwards, which includes the Pro 3EM, the documentation says: “By default, no additional configuration is required.” Two things are still worth knowing:

The Pro 3EM has two profiles. In the default triphase profile it is a single three-phase meter with per-phase values and totals across all phases. In the monophase profile it becomes three separate single-phase meters, for example for three individual circuits. For the grid connection, triphase is correct.

Assigning import, export and power

In the triphase profile the integration creates three total sensors alongside the per-phase values, and those are the ones that belong in the dashboard:

The Pro 3EM's total sensors in Home Assistant
SensorValue in the deviceIn the Energy dashboard
Energy (kWh)total_actenergy from the grid
Energy returned (kWh)total_act_retenergy to the grid
Power (W)total_act_power, “Sum of the active power on all phases”power measurement of the grid connection

This is set under Settings › Dashboards › Energy, under Electricity grid with Add grid connection. Home Assistant expects power to be positive when importing and negative when exporting; that is how the Shelly delivers it when the transformers are fitted the right way round. For devices that count the other way, there is the Inverted setting. Anyone who needs to split by tariff periods uses the utility_meter integration.

Netting: why the Shelly and the utility meter count differently

This is the difference the dashboard does not notice on its own. A German utility meter counts on a netted basis. The specification for the basic meter, to which modern metering devices in Germany are built, puts it briefly: “The measurement is always made as the sum across all phase conductors.” If phase L1 is drawing 2 kW while a balcony PV system on L2 feeds in 600 W, the meter counts 1.4 kW of import and no export.

The Shelly, on the other hand, keeps its energy counters per phase, separately for import and return: for phases A, B and C one counter each for imported and one for returned energy, plus the totals across all phases. For netted values Shelly offers a separate query, EMData.GetNetEnergies, with periods of 5 to 60 minutes. So the normal counters are not netted. In the example, both rise on the Shelly: the import counter with 2 kW, the export counter with 600 W.

In the dashboard this looks harmless, but it is not. Grid import and export come out higher than what is billed, the PV system's self-consumption too low and the costs too high. It only does not matter as long as no phase flows in the opposite direction, that is, in a house without generation.

The good news: the Shelly's total power is already netted; it is the sum of the active power of all phases. From it, Home Assistant can build two counters that count the way the utility meter does. First two template sensors that split power by direction:

template:
  - sensor:
      - name: "Grid import power"
        unique_id: grid_import_power
        unit_of_measurement: "W"
        device_class: power
        state_class: measurement
        availability: "{{ has_value('sensor.pro3em_power') }}"
        state: "{{ [states('sensor.pro3em_power') | float(0), 0] | max }}"
      - name: "Grid export power"
        unique_id: grid_export_power
        unit_of_measurement: "W"
        device_class: power
        state_class: measurement
        availability: "{{ has_value('sensor.pro3em_power') }}"
        state: "{{ [0 - states('sensor.pro3em_power') | float(0), 0] | max }}"

Then an energy counter from each with the integration integration, the Riemann sum. It is also available as a helper in the interface:

sensor:
  - platform: integration
    source: sensor.grid_import_power
    name: Grid import netted
    unit_prefix: k
    method: left
    round: 3
    max_sub_interval:
      minutes: 1
  - platform: integration
    source: sensor.grid_export_power
    name: Grid export netted
    unit_prefix: k
    method: left
    round: 3
    max_sub_interval:
      minutes: 1

sensor.pro3em_power stands for your own device's total power sensor. The two new counters have device class energy and state class total and are entered in the dashboard instead of the Shelly counters; the total power remains the Shelly's.

On the choice of method: the Shelly reports a new power value as soon as it has changed by 5 % or by 10 W. In between, the old value applies. That is exactly what the left method assumes; the documentation recommends it for sources that hold their value for long periods. max_sub_interval makes sure the calculation continues regularly even when power is constant.

A Riemann sum is an approximation, as the documentation itself says: “intrinsically inaccurate”. How well it matches only shows when you reconcile against the meter. Newly created counters start at zero; the statistics of the Shelly counters remain alongside.

Reconciling against the meter

The step that makes the numbers reliable: note the meter readings for import and export, wait a fixed period, read again and compare with the totals in the dashboard. According to Shelly, the Pro 3EM measures with ±1 % from 2 A; at small currents it becomes less accurate. If the deviation is clearly larger, the usual suspects are a transformer fitted the wrong way round, a transformer on the wrong phase or the missing netting. How to reconcile in practice is described in Energy metering in the distribution board.

Solar, battery and individual devices

At the grid connection the Shelly only sees what flows across the connection. What the PV system produces therefore comes from a separate source, usually the inverter's integration, as do the battery's charge and discharge. Only with both can the dashboard work out what the house actually consumed. How battery and inverter get into Home Assistant is covered in Controlling a home battery with Home Assistant.

Individual devices, for example via smart plugs or sub-meters, are entered under Individual devices. If one meter measures a whole circuit and a second one a device on it, the Upstream device setting prevents consumption being counted twice. If a device only provides power, the Riemann sum above turns it into an energy counter. What a single device costs per year can be estimated beforehand with the electricity cost calculator on xmoo.app (in German); the measurement in the dashboard then shows whether the estimate holds.

Seeing the energy flow

Showing the energy flow needs no extra card. Home Assistant comes with several, and all of them can be placed on any other page outside the Energy dashboard too:

Built-in cards for the energy flow
CardShowsTime reference
Energy distribution (energy-distribution)flow between grid, solar, battery and houseselected period
Sankey energy graph (energy-sankey)flow from sources to consumers, grouped by floors and areasselected period
Power flow Sankey graph (power-sankey)current power as a flownow, independent of the date picker
Power sources graph (power-sources-graph)power of the sources over timehistory
Power consumption badge (power-total)current total power of the house from grid, solar and batterynow

Which cards the Energy dashboard itself shows can be set under Settings › Dashboards › Energy › Edit dashboard › Customize cards. The selection applies to the whole system, not just your own browser.

Typical mistakes

Frequently asked questions

Which Shelly Pro 3EM sensors belong in the Energy dashboard?

Three for the grid connection: the total counter for imported energy (“Energy” in the English interface), the one for returned energy (“Energy returned”) and the total power across all phases (“Power”). The per-phase sensors do not belong there. If a PV system feeds in within the house, self-built netted counters are the more accurate choice.

Why does Home Assistant show more export with the Shelly Pro 3EM than the utility meter?

Because the utility meter nets across all phases, whereas the Shelly's energy counters count import and return per phase. If one phase exports while another imports, both Shelly counters rise, while the utility meter only counts the difference. The remedy is counters that Home Assistant builds from the Shelly's netted total power.

Do I need MQTT for the Shelly Pro 3EM in Home Assistant?

No. The Shelly integration talks to the device locally, and devices from the second generation onwards push their values to Home Assistant by themselves. Mains-powered devices need no additional settings for this.

Is there an energy flow card in Home Assistant without extra installation?

Yes. The energy distribution card shows how energy flowed between grid, solar, battery and house in the selected period. For the present moment there is the power-sankey card, which shows current power as a flow and is independent of the date picker.

What is the difference between the Shelly Pro 3EM and the Pro 3EM-3CT63?

The measuring range and the current transformers. The Pro 3EM measures up to 120 A per phase with three individual transformers, the Pro 3EM-3CT63 up to 63 A with a combined three-phase transformer mounted over a circuit breaker. There is also the Pro 3EM-400 for up to 400 A.

Why does the Shelly Pro 3EM show negative power when importing?

Usually a current transformer is fitted the wrong way round. The measuring direction can be reversed per phase in the device configuration, after which the device restarts. Whether all three phases are right is shown by the per-phase power values under a known load.

Sources

All statements come from the documentation of Home Assistant and Shelly, the source code of the Shelly integration and the specification for the German basic meter, each with the date it was checked. Quotations from German documents are my translation.

Home Assistant and the Shelly firmware change continuously. The current documentation is what counts. Work in the meter cabinet is reserved for a qualified electrician.

Links marked with an asterisk are affiliate links. As an Amazon Associate I earn from qualifying purchases; the price is unchanged for you. What I recommend does not depend on it.

Your Energy dashboard shows different numbers from the utility meter, and you want to know why? I can take a look at your system – the first conversation is free.