Technical article · Grid operator · Heilbronn region

Section 14a EnWG at NHF and NHL in Heilbronn

The Federal Network Agency's determination applies nationwide; the grid operator fills in the details. In Heilbronn and seven neighbouring municipalities these are NHF Netzgesellschaft Heilbronn-Franken and NHL Netzgesellschaft Heilbronner Land. Their requirements differ markedly from those of Netze BW in several places. This page collects them, each with document and date checked.

Applies to
low voltage at NHF (Heilbronn, Lauffen, Kirchheim, Neckarwestheim) and NHL (Leingarten, Flein, Talheim, Untergruppenbach)
Control
preventive via radio ripple control receiver, at most 2 hours a day
Meter location
additional space for supplementary applications with 12 modules and a customer-owned 230 V coupling relay
Grid fee 2026
module 1 as default: 152.83 € a year incl. VAT
Documents
technical minimum requirements section 14a, supplement to TAB 2026, price sheet 2026
Status
October 2026 · primary sources below, with the date each was checked
Author
Julian Haag, state-certified electrical engineering technician

Your electricity bill shows which grid operator is responsible for your connection. The basics that are the same for all grid operators are in the guide to section 14a EnWG; what Netze BW requires is in the article Section 14a EnWG at Netze BW.

Grid area and documents

NHF's supplement to the TAB 2026, valid from 1 November 2026, shows the supply area on a map: NHF supplies Heilbronn, Lauffen, Kirchheim and Neckarwestheim, NHL Leingarten, Flein, Talheim and Untergruppenbach. Both companies are based in Weipertstraße in Heilbronn, and their documents apply to both grid areas.

What counts for section 14a are the technical minimum requirements for grid-oriented control (TMA). The document is marked “1st edition December 2023”; the PDF on the website dates from February 2024. The supplement to the TAB 2026 still refers to exactly this TMA for control under section 14a. It is therefore considerably older than other grid operators' versions from this year; what it says about the preventive phase describes the state NHF itself presents as valid.

What counts as a controllable consumption device

NHF adopts the four groups of the determination: private charging points, heat pump heating including supplementary and emergency heating, room cooling systems and battery storage, each with more than 4.2 kW connected load. Heat pumps and air conditioners of the same kind behind one grid connection are added together; NHF's example is three air conditioners of 2.5 kW each in an apartment building, together 7.5 kW and therefore one controllable consumption device. Devices up to 4.2 kW must still be reported but may not take part in section 14a.

There are three clarifications that are not in every TMA:

Also exempt from the obligation are charging points of institutions with special rights under section 35 of the German road traffic regulations and heat pumps or air conditioners not used for heating or cooling rooms, for example for commercial purposes or in critical infrastructure. How the 4.2 kW threshold is meant is explained in the article The 4.2 kW in section 14a EnWG.

Registration

Every commissioning of a controllable consumption device must be notified to NHF in advance; the TMA cites section 19(2) of the German low-voltage connection ordinance for this. If the connection needs more capacity, that too must be applied for beforehand, and decommissioning must also be reported. According to NHF, commissioning must be carried out by a registered electrician. Registration is via NHF's grid connection portal.

How NHF controls

This is the most striking difference from other grid operators. Until grid-oriented control is released, preventive control applies in NHF's grid area according to the TMA, and it works via a radio ripple control receiver in DIN-rail design. NHF determines when it is needed and installs the control equipment in the customer's installation.

In the later grid-oriented phase, stepless control between minimum and maximum power is to become possible. NHF writes on its website that control will “only be necessary in absolute emergencies” and that normal household consumption remains unaffected. What happens technically during curtailment is explained in the article What curtailment does in practice.

Minimum power and energy management

The TMA works through how far a system must go down, using the Federal Network Agency's values:

Simultaneity factor by number of systems on the EMS (NHF TMA)
Systems23456789+
Factor0.80.750.70.650.60.550.50.45

For heat pumps and air conditioners up to 11 kW the formula is: 4.2 kW plus (number of systems minus one) times factor times 4.2 kW. NHF's worked example: a 9 kW heat pump and three 11 kW wallboxes are four systems, so 4.2 kW + 3 × 0.7 × 4.2 kW = 13.02 kW that the EMS may draw in total during the control period. Above 11 kW the first 4.2 kW is replaced by the larger of 0.4 × the total of the heat pumps or 0.4 × the total of the air conditioners.

The meter location: coupling relay instead of terminal strip

At Netze BW and Netze ODR the interface to the customer is an RJ-45 socket with EEBUS, plus a control signal terminal strip. NHF's TMA describes a different set-up:

NHF also recommends a further DIN rail of at least 12 modules, for future control and for value-added services at the smart meter gateway, for example a CLS switch or a further control box. The December 2023 TMA does not mention a digital interface such as EEBUS.

In existing installations

Existing meter locations according to NHF TMA, section 6.3
ExistingSolution
one meter fieldDIN rail of at least 12 modules in the customer installation, otherwise an external distribution board at the meter location; Cat 5 with RJ-45 at both ends, power supply
free control device or meter field (three-point)use this field; retrofit power supply, coupling relay above it
three-point, at least two meter fields, no control device or distribution fieldexternal distribution board with at least 3 DIN rails of 12 modules each, power supply and Cat 5
plug-in technology, at least two meter fieldsexisting space for supplementary applications suffices

What the three routes look like at Netze BW and how much space the control box needs there is in the article Control box in an old meter cabinet.

Grid fees 2026

Without a choice of your own, module 1 applies. The choice between module 1 and 2 exists only for consumption without load profile metering; according to the TMA it is possible up to an annual consumption of 100,000 kWh. The prices from price sheet 3a, including VAT:

NHF section 14a grid fees 2026, incl. VAT, consumption without load profile metering
ModulePriceRequirement
Module 1 – flat ratecredit 152.83 €/yeardefault; grid fee never below 0.00 €
Module 2 – energy price3.88 ct/kWh instead of 9.71 ct/kWhseparate metering; only controllable devices on that circuit
Module 3 – low tariff, 0–6 am3.88 ct/kWhonly with module 1 and a smart metering system; in 2026 in all four quarters
Module 3 – standard tariff, 6 am–5 pm and 8 pm–midnight9.71 ct/kWh
Module 3 – high tariff, 5–8 pm15.54 ct/kWh

The standing charge is 91.63 € a year including VAT. NHF's low-tariff window is at night, Netze BW's at midday. Anyone who can shift a heat pump or a car in time plans differently here: charge and preheat at night rather than at midday.

According to the TMA, NHF no longer implements tariff switching. Anyone who wants time-dependent tariffs needs a smart metering system and gets the tariff from their supplier. For separate metering in cascade on electronic household meter locations, the TMA requires a disconnection point after the first meter and before and after the second.

Which module pays off at which consumption is in the article Section 14a: module 1, 2 or 3?; the grid fee calculator works with your own figures.

Existing systems

Heat pumps and charging equipment above 4.2 kW that were already operated under the old section 14a before 1 January 2024 can switch to the new scheme on request and must do so by 31 December 2028 at the latest. There is no way back into the old contract afterwards. Systems that did not previously run under section 14a may switch if they implement the TMA. According to NHF, night storage heaters have permanent protection. Anyone operating existing systems without an old contract need not do anything. The general rules are in the article Section 14a EnWG for existing systems.

Compared with Netze BW

NHF and Netze BW under section 14a, according to both operators' documents
NHF / NHLNetze BW
Preventive controlradio ripple control receiver, times per feederfixed time switch, until the end of 2028 at the latest
Interface to the customercustomer-owned 230 V coupling relayRJ-45 with EEBUS, plus terminal strip for analogue control
TMA versionDecember 2023version 1.0 of April 2026
Module 1, incl. VAT152.83 €/year147.56 €/year
Module 2, incl. VAT3.88 instead of 9.71 ct/kWh3.61 instead of 9.01 ct/kWh
Module 3 low tariff0–6 am10 am–2 pm

For the electrician this means: an installation that fits in Netze BW's grid area is not automatically right at NHF, and vice versa. Before ordering, it pays to check who operates the connection.

Frequently asked questions

Which places do NHF and NHL supply?

According to the supplement to the TAB 2026, NHF Netzgesellschaft Heilbronn-Franken supplies Heilbronn, Lauffen, Kirchheim and Neckarwestheim, and NHL Netzgesellschaft Heilbronner Land supplies Leingarten, Flein, Talheim and Untergruppenbach. The same technical minimum requirements for section 14a apply to both. Your electricity bill shows which grid operator is responsible.

How does NHF control a heat pump or wallbox under section 14a?

According to its technical minimum requirements, preventive control applies until grid-oriented control is released. NHF installs a DIN-rail radio ripple control receiver where needed and controls for at most two hours a day, at times it sets per low-voltage feeder, for example 7 to 9 pm. During that time each system must reduce to 4.2 kW or, if that is not possible, to 0 kW.

What must be prepared in the meter cabinet for section 14a at NHF?

In new installations, an additional space for supplementary applications with a 12-module DIN rail above the APZ field, containing a customer-owned 230 V coupling relay up to whose contacts the control line to the device or energy management system is prepared. Plus the power supply for the space for supplementary applications and the APZ according to VDE-AR-N 4100 and a data cable of at least Cat 5 between the two.

How high is the reduced grid fee at NHF in 2026?

Module 1 gives a credit of 152.83 euros a year including VAT. Module 2 lowers the energy price to 3.88 cents per kilowatt hour including VAT instead of 9.71 cents but requires separate metering. In 2026 module 3 applies in all four quarters with a low tariff from midnight to 6 am and a high tariff from 5 to 8 pm, and can only be chosen together with module 1 and a smart metering system.

Does NHF still offer tariff switching for heat pumps?

No. NHF states in its technical minimum requirements that it no longer implements tariff switching. Anyone who still wants time-dependent tariffs needs a smart metering system and gets the tariff from their electricity supplier.