Technical article · Grid operator · Heilbronn region
Section 14a EnWG at NHF and NHL in Heilbronn
The Federal Network Agency's determination applies nationwide; the grid operator fills in the details. In Heilbronn and seven neighbouring municipalities these are NHF Netzgesellschaft Heilbronn-Franken and NHL Netzgesellschaft Heilbronner Land. Their requirements differ markedly from those of Netze BW in several places. This page collects them, each with document and date checked.
Your electricity bill shows which grid operator is responsible for your connection. The basics that are the same for all grid operators are in the guide to section 14a EnWG; what Netze BW requires is in the article Section 14a EnWG at Netze BW.
Grid area and documents
NHF's supplement to the TAB 2026, valid from 1 November 2026, shows the supply area on a map: NHF supplies Heilbronn, Lauffen, Kirchheim and Neckarwestheim, NHL Leingarten, Flein, Talheim and Untergruppenbach. Both companies are based in Weipertstraße in Heilbronn, and their documents apply to both grid areas.
What counts for section 14a are the technical minimum requirements for grid-oriented control (TMA). The document is marked “1st edition December 2023”; the PDF on the website dates from February 2024. The supplement to the TAB 2026 still refers to exactly this TMA for control under section 14a. It is therefore considerably older than other grid operators' versions from this year; what it says about the preventive phase describes the state NHF itself presents as valid.
What counts as a controllable consumption device
NHF adopts the four groups of the determination: private charging points, heat pump heating including supplementary and emergency heating, room cooling systems and battery storage, each with more than 4.2 kW connected load. Heat pumps and air conditioners of the same kind behind one grid connection are added together; NHF's example is three air conditioners of 2.5 kW each in an apartment building, together 7.5 kW and therefore one controllable consumption device. Devices up to 4.2 kW must still be reported but may not take part in section 14a.
There are three clarifications that are not in every TMA:
- Instantaneous water heaters and direct electric heating are not controllable consumption devices and may not be connected for grid-oriented control.
- Electric hot water storage tanks without a heat pump operating at the same time may not be operated under section 14a.
- Electric storage heaters are excluded, and voluntary switching into the scheme is not possible for them.
Also exempt from the obligation are charging points of institutions with special rights under section 35 of the German road traffic regulations and heat pumps or air conditioners not used for heating or cooling rooms, for example for commercial purposes or in critical infrastructure. How the 4.2 kW threshold is meant is explained in the article The 4.2 kW in section 14a EnWG.
Registration
Every commissioning of a controllable consumption device must be notified to NHF in advance; the TMA cites section 19(2) of the German low-voltage connection ordinance for this. If the connection needs more capacity, that too must be applied for beforehand, and decommissioning must also be reported. According to NHF, commissioning must be carried out by a registered electrician. Registration is via NHF's grid connection portal.
How NHF controls
This is the most striking difference from other grid operators. Until grid-oriented control is released, preventive control applies in NHF's grid area according to the TMA, and it works via a radio ripple control receiver in DIN-rail design. NHF determines when it is needed and installs the control equipment in the customer's installation.
- Control lasts at most two hours a day, possibly split up.
- The times are not fixed; NHF sets them per low-voltage feeder of each local substation, giving 7 to 9 pm as an example.
- During the control period each system must individually reduce to 4.2 kW. If it cannot, it must go to 0 kW. With an energy management system, the participating systems may together draw the minimum power described in the next section.
In the later grid-oriented phase, stepless control between minimum and maximum power is to become possible. NHF writes on its website that control will “only be necessary in absolute emergencies” and that normal household consumption remains unaffected. What happens technically during curtailment is explained in the article What curtailment does in practice.
Minimum power and energy management
The TMA works through how far a system must go down, using the Federal Network Agency's values:
- Heat pumps and air conditioners up to 11 kW (individually or in total) reduce to 4.2 kW.
- Above 11 kW a scaling factor of 0.4 applies to the connected load. NHF's example: a 15 kW heat pump including immersion heater must reduce to 6 kW.
- With an energy management system a simultaneity factor is added for each further system.
| Systems | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9+ |
|---|---|---|---|---|---|---|---|---|
| Factor | 0.8 | 0.75 | 0.7 | 0.65 | 0.6 | 0.55 | 0.5 | 0.45 |
For heat pumps and air conditioners up to 11 kW the formula is: 4.2 kW plus (number of systems minus one) times factor times 4.2 kW. NHF's worked example: a 9 kW heat pump and three 11 kW wallboxes are four systems, so 4.2 kW + 3 × 0.7 × 4.2 kW = 13.02 kW that the EMS may draw in total during the control period. Above 11 kW the first 4.2 kW is replaced by the larger of 0.4 × the total of the heat pumps or 0.4 × the total of the air conditioners.
The meter location: coupling relay instead of terminal strip
At Netze BW and Netze ODR the interface to the customer is an RJ-45 socket with EEBUS, plus a control signal terminal strip. NHF's TMA describes a different set-up:
- New installation, direct metering: power supply for the space for supplementary applications and the APZ according to VDE-AR-N 4100, a data cable of at least Cat 5 between the two, and an additional space for supplementary applications with a 12-module DIN rail above the APZ field.
- This space houses a customer-owned 230 V coupling relay. The control line to the device or the energy management system is prepared up to its working contacts. When NHF issues a control command, the relay picks up with 230 V.
- Meter locations: locations with integrated mounting and contacting device (BKE-I) for electronic household meters are approved, fitted with adapter plate BKE-AZ and BKE data interface.
- Two plug-in meters need no additional space; the existing one suffices. With three or more meters it is always required, in the cabinet with the APZ, and the meter cabinets are connected with Cat 5.
- Transformer metering: the coupling relay sits in the installation-side connection space above the meter field.
NHF also recommends a further DIN rail of at least 12 modules, for future control and for value-added services at the smart meter gateway, for example a CLS switch or a further control box. The December 2023 TMA does not mention a digital interface such as EEBUS.
In existing installations
| Existing | Solution |
|---|---|
| one meter field | DIN rail of at least 12 modules in the customer installation, otherwise an external distribution board at the meter location; Cat 5 with RJ-45 at both ends, power supply |
| free control device or meter field (three-point) | use this field; retrofit power supply, coupling relay above it |
| three-point, at least two meter fields, no control device or distribution field | external distribution board with at least 3 DIN rails of 12 modules each, power supply and Cat 5 |
| plug-in technology, at least two meter fields | existing space for supplementary applications suffices |
What the three routes look like at Netze BW and how much space the control box needs there is in the article Control box in an old meter cabinet.
Grid fees 2026
Without a choice of your own, module 1 applies. The choice between module 1 and 2 exists only for consumption without load profile metering; according to the TMA it is possible up to an annual consumption of 100,000 kWh. The prices from price sheet 3a, including VAT:
| Module | Price | Requirement |
|---|---|---|
| Module 1 – flat rate | credit 152.83 €/year | default; grid fee never below 0.00 € |
| Module 2 – energy price | 3.88 ct/kWh instead of 9.71 ct/kWh | separate metering; only controllable devices on that circuit |
| Module 3 – low tariff, 0–6 am | 3.88 ct/kWh | only with module 1 and a smart metering system; in 2026 in all four quarters |
| Module 3 – standard tariff, 6 am–5 pm and 8 pm–midnight | 9.71 ct/kWh | |
| Module 3 – high tariff, 5–8 pm | 15.54 ct/kWh |
The standing charge is 91.63 € a year including VAT. NHF's low-tariff window is at night, Netze BW's at midday. Anyone who can shift a heat pump or a car in time plans differently here: charge and preheat at night rather than at midday.
According to the TMA, NHF no longer implements tariff switching. Anyone who wants time-dependent tariffs needs a smart metering system and gets the tariff from their supplier. For separate metering in cascade on electronic household meter locations, the TMA requires a disconnection point after the first meter and before and after the second.
Which module pays off at which consumption is in the article Section 14a: module 1, 2 or 3?; the grid fee calculator works with your own figures.
Existing systems
Heat pumps and charging equipment above 4.2 kW that were already operated under the old section 14a before 1 January 2024 can switch to the new scheme on request and must do so by 31 December 2028 at the latest. There is no way back into the old contract afterwards. Systems that did not previously run under section 14a may switch if they implement the TMA. According to NHF, night storage heaters have permanent protection. Anyone operating existing systems without an old contract need not do anything. The general rules are in the article Section 14a EnWG for existing systems.
Compared with Netze BW
| NHF / NHL | Netze BW | |
|---|---|---|
| Preventive control | radio ripple control receiver, times per feeder | fixed time switch, until the end of 2028 at the latest |
| Interface to the customer | customer-owned 230 V coupling relay | RJ-45 with EEBUS, plus terminal strip for analogue control |
| TMA version | December 2023 | version 1.0 of April 2026 |
| Module 1, incl. VAT | 152.83 €/year | 147.56 €/year |
| Module 2, incl. VAT | 3.88 instead of 9.71 ct/kWh | 3.61 instead of 9.01 ct/kWh |
| Module 3 low tariff | 0–6 am | 10 am–2 pm |
For the electrician this means: an installation that fits in Netze BW's grid area is not automatically right at NHF, and vice versa. Before ordering, it pays to check who operates the connection.
Frequently asked questions
Which places do NHF and NHL supply?
According to the supplement to the TAB 2026, NHF Netzgesellschaft Heilbronn-Franken supplies Heilbronn, Lauffen, Kirchheim and Neckarwestheim, and NHL Netzgesellschaft Heilbronner Land supplies Leingarten, Flein, Talheim and Untergruppenbach. The same technical minimum requirements for section 14a apply to both. Your electricity bill shows which grid operator is responsible.
How does NHF control a heat pump or wallbox under section 14a?
According to its technical minimum requirements, preventive control applies until grid-oriented control is released. NHF installs a DIN-rail radio ripple control receiver where needed and controls for at most two hours a day, at times it sets per low-voltage feeder, for example 7 to 9 pm. During that time each system must reduce to 4.2 kW or, if that is not possible, to 0 kW.
What must be prepared in the meter cabinet for section 14a at NHF?
In new installations, an additional space for supplementary applications with a 12-module DIN rail above the APZ field, containing a customer-owned 230 V coupling relay up to whose contacts the control line to the device or energy management system is prepared. Plus the power supply for the space for supplementary applications and the APZ according to VDE-AR-N 4100 and a data cable of at least Cat 5 between the two.
How high is the reduced grid fee at NHF in 2026?
Module 1 gives a credit of 152.83 euros a year including VAT. Module 2 lowers the energy price to 3.88 cents per kilowatt hour including VAT instead of 9.71 cents but requires separate metering. In 2026 module 3 applies in all four quarters with a low tariff from midnight to 6 am and a high tariff from 5 to 8 pm, and can only be chosen together with module 1 and a smart metering system.
Does NHF still offer tariff switching for heat pumps?
No. NHF states in its technical minimum requirements that it no longer implements tariff switching. Anyone who still wants time-dependent tariffs needs a smart metering system and gets the tariff from their electricity supplier.
Sources
All statements come from NHF's documents, each with the date it was checked. According to NHF, the TMA also applies to NHL. In case of deviations, the grid operator's documents in their current version apply. The source documents are in German; quotations are my translation.
- TMA NHF – technical minimum requirements for grid-oriented control under section 14a EnWG (PDF) 1st edition December 2023, PDF of 21.02.2024; scope NHF and NHL, controllable devices, exemptions, existing systems, modules, no tariff switching, preventive control via radio ripple control receiver, minimum power, simultaneity factor, meter location with coupling relay, existing meter locations. Checked on 08.10.2026.
- TAB NHF – supplement to TAB 2026 low voltage (PDF) As of 30.09.2026, valid from 01.11.2026; supply area NHF and NHL; registration via the grid connection portal; reference to the TMA for section 14a. Checked on 08.10.2026.
- Price sheet NHF – price sheets electricity 2026 Price sheet 3 (standard grid fee) and 3a (modules 1 to 3, module 3 tariff times), prices valid from 01.01.2026. Checked on 08.10.2026.
- Website NHF – new section 14a EnWG rules FAQ: control only in emergencies, minimum power, registered electrician, protection of existing systems, transfer by end of 2028, night storage heaters. Checked on 08.10.2026.
Haag Automation has no business relationship with NHF or NHL. The grid operator's documents and information are binding.
You are planning a heat pump, wallbox or battery in NHF's grid area and need the single-line diagram for the registration? I can draw it for you – or write to me about control and energy management.