Fronius Wattpilot and section 14a EnWG

Fronius describes section 14a in the operating instructions of the Wattpilot models: control runs via a digital input that not every model has. And there is a requirement you would not expect on a wallbox: in Germany the Wattpilot must be permanently connected to the internet.

Models
Wattpilot Flex (Home and Pro), Wattpilot Home 2.0
Route
digital input, connected to the control box or ripple control receiver
Online requirement
permanent in Germany, for documentation under section 14a
Manufacturer sources
operating instructions Wattpilot Flex (edition 008-18082026) and Wattpilot Go/Home 2.0 (edition 019-19082026)
Status
October 2026 · primary sources below, with the date each was checked
Author
Julian Haag, state-certified electrical engineering technician

The digital input

Wattpilot Flex. “The Fronius Wattpilot Flex is equipped with a digital input (DI_1). The digital input in the mains supply line can limit the charging current.” Among the use cases, Fronius explicitly names connection to a ripple control receiver and “use of the Wattpilot Flex as a controllable consumer under section 14a EnWG”. Configuration is done in the Solar.wattpilot app: activating the digital input and configuring the switch contacts.

The Flex instructions set a condition that matters for wiring: if the insulation requirements are not observed, the Wattpilot and connected components can be damaged. “Only use permanently installed switching devices of overvoltage category 3 (according to EN IEC 60664-1).” The technical data list two non-isolated inputs.

Wattpilot Home 2.0. “The digital input can be used with the Fronius Wattpilot Home 2.0.” It limits the charging current, for example “for the grid operator to connect a ripple control receiver”. The contact logic is selectable: as normally open (NO), the red and white wires must be connected for the limit to apply; as normally closed (NC), they must not be connected for it. The settings can be protected with the technician password.

Wattpilot Go 2.0. The instructions for the 2.0 models name the digital input only for the Home 2.0. For the Go 2.0 they describe no connection to a control box.

Which charging current remains during curtailment is part of the input's configuration. Under direct control the grid operator must leave at least 4.2 kW (clause 4.5.1 of the ruling); the wallbox may take less, not more.

Fronius Wattpilot: which model has an input and how the contact works Top: three models. Wattpilot Flex with input DI_1 and Home 2.0 with red and white wires have a digital input; the manual describes none for the Go 2.0. Below, the Home 2.0 contact logic: as normally open the limit applies when red and white are connected, as normally closed when they are open. At the bottom, the note that in Germany the Wattpilot must be permanently online for proof under section 14a. Wattpilot Flex input DI_1 Home 2.0 red/white wires Go 2.0 no input Home 2.0: when the limit applies normally open (NO) red white connected= limited normally closed (NC) red white open= limited Permanently online in Germany: proof under section 14a
Based on the operating instructions for the Wattpilot Flex (008-18082026) and Go/Home 2.0 (019-19082026). For the Flex, in addition: only permanently installed switchgear of overvoltage category 3.

Permanently online – why

Both instructions contain the same sentence: “In Germany, the Wattpilot must be permanently connected to the internet to fulfil the documentation obligation under section 14a EnWG, so that implementation of external control commands can be proven.”

The obligation behind it is in the Bundesnetzagentur's ruling: the operator must ensure that implementation of a requested reduction “can be traceably demonstrated to the grid operator in each individual case” (clause 7.2). The information must be “kept for at least 2 years after the measure” (clause 7.3) and presented to the grid operator if there are justified doubts (clause 7.4).

In practice: with the Wattpilot, the Wi-Fi in the garage is part of the section 14a installation. If it drops out, the proof Fronius keeps via the connection has a gap. Anyone running an energy management system or Home Assistant anyway can log the interventions themselves as well.

And EEBUS?

EEBUS does not appear in either Wattpilot manual; the route described is the contact on the digital input. If the metering point operator's control box only controls digitally via EEBUS, an energy management system is needed in between. Which control the responsible grid operator provides for is set out in its technical connection conditions.

Frequently asked questions

How does the Fronius Wattpilot meet section 14a EnWG?

Via the digital input: the contact of the control box or ripple control receiver is connected to the input, which limits the charging current. Fronius describes this for the Wattpilot Flex and the Wattpilot Home 2.0; the input is configured in the Solar.wattpilot app.

Does the Wattpilot Go 2.0 have an input for the control box?

The operating instructions for the 2.0 models name the digital input only for the Wattpilot Home 2.0. For the Go 2.0 they describe no connection to a control box.

Why must the Wattpilot be online permanently?

Fronius writes that in Germany the Wattpilot must be permanently connected to the internet to fulfil the documentation obligation under section 14a EnWG, so that implementation of external control commands can be proven. The Bundesnetzagentur's ruling obliges the operator to be able to show traceably how a reduction was implemented and to keep this information for at least two years.

Sources

The manufacturer information comes exclusively from the manufacturer's own documents, each with its date and the date it was checked. Manufacturer documents change with every firmware release; what counts is the version valid at the time of installation. Quotations from German documents are our translation.

This article reproduces manufacturer information; it replaces neither Fronius's documentation nor the technical connection conditions of your grid operator. Connection and registration are reserved for a registered electrical contractor. Haag Automation has no business relationship with Fronius.