Heat pump · Dynamic tariff
Running a heat pump on electricity prices
Relay contact, Modbus or the manufacturer's cloud – which route holds up, what funding has required since July 2026, and where control runs into its limits.
Read the article →Technical article · Manufacturers
Daikin names three routes by which an Altherma implements control under section 14a. They differ in what happens during curtailment – off, throttled, or throttled with feedback – and since July 2026 also in whether a newly installed heat pump can still be subsidised. This page sets out what Daikin itself publishes, with the date of each document, and shows where those documents contradict each other.
Daikin's section 14a leaflet opens with a clear statement: “All DAIKIN Altherma heat pumps fall under the regulation and must therefore be fitted with an appropriate contact.” It then describes three options that differ above all in what the heat pump does when the grid operator curtails it.
| Route | Accessory | During curtailment | Feedback |
|---|---|---|---|
| 1 · Utility contact | none | heat pump switches off | no |
| 2 · Relay contact with power limit | communication board EKRP1AHTA; built in on Altherma 4 and GEO | auxiliary heater off, outdoor unit throttled to a set limit | no |
| 3 · Digital interface | Daikin HomeHub EKRHH, EEBUS | limited to the requested value | yes: consumption measurement, event log |
According to Daikin, all Altherma heat pumps already meet the requirement today “through grid-supportive behaviour by using the so-called utility (EVU) contact, which leads to the unit being switched off”. No extra accessory is needed.
Legally, that holds. Clause 4.6 of ruling BK6-22-300 covers exactly this case: if an installation cannot, for technical reasons, reduce to the requested value, “it must be reduced to the next lower value that is technically possible”. For a device that only knows on and off, that means off. The reasoning of the ruling also makes clear that an installation which can only be switched off completely is not exempt from participation for that reason.
The price: under direct control the ruling guarantees a minimum power of 4.2 kW – a heat pump that can only switch off gains nothing from that. It stands still for as long as the grid operator is curtailing. How often and for how long that happens in practice is covered in What curtailment does in practice.
With the communication board EKRP1AHTA in the indoor unit, switching off becomes throttling. Daikin describes it as “limiting power consumption by setting a maximum current draw or power limit to be defined”: during curtailment “the auxiliary heater is deactivated and the current draw of the outdoor unit is ‘dimmed’”.
On the Altherma 4 and the Altherma GEO this function is already built into the unit; no separate board is needed.
Important for commissioning: here too, the command arrives via a contact. The contact only tells the heat pump that it should limit, not to what value. The limit is a parameter set during commissioning – and it has to match the minimum power the grid operator must allow.
The third route is the one section 14a is really aiming at: a digital interface. The Daikin HomeHub (part number EKRHH) receives the control box's instruction via EEBUS and implements it in the heat pump. According to Daikin, the same interface also connects energy management systems that speak EEBUS or Modbus TCP/IP.
Here Daikin's documents contradict each other. The section 14a leaflet (as of March 2025) and the section 14a page on daikin.de (retrieved on 7 October 2026) still describe route 3 as “planned”: the function “will become available in due course and can be implemented after a system update”. The HomeHub installer reference guide, edition 2026.01, on the other hand describes the same use case in full – control “directly by the control box (CB) of the power grid”, including a compatibility list, minimum firmware and behaviour on loss of connection. If you rely on route 3, get written confirmation from the manufacturer or wholesaler that the use case is available for the specific installation.
The HomeHub reference guide lists which combinations of outdoor and indoor unit are supported for the EEBUS use case. The model designation is on the rating plate; the leading letters identify the series.
| Series | Outdoor unit | Indoor unit |
|---|---|---|
| Altherma 3 H HT | EPRA14/16/18DV37/W17 | ETVH/X/Z16-E7, ETSH(B)/X(B)16-E7, ETBH/X16-E7 |
| Altherma 3 H MT | EPRA08/10/12EV3/W1 | ETVH/X/Z12-E, ETSH(B)/X(B)12-P-E, ETBH/X12-E |
| Altherma 3 R | ERGA-EV(7)(H)(A) | EHVH/X/Z-E, EHSH(B)/X(B)-P-E, EHBH/X-E |
| Altherma 3 R | ERLA11/14/16DV3/W1 | EBVH/X/Z-D, EBSH(B)/X(B)-D, EBBH/EBBX-D |
| Altherma 3 R MT | ERRA-EV3/W1 | ELVH/X/Z-E, ELSH(B)/X(B)-E, ELBH/X-E |
| Altherma 3 M | EBLA/EDLA09/11/14/16D, EBLA/EDLA04/06/08E | no indoor unit |
An example: the combination of indoor unit ELBX12E9W and outdoor unit ERRA10EW1 falls under “ELBH/X-E” and “ERRA-EV3/W1” – an Altherma 3 R MT, and therefore on the list.
Two series are missing from this list:
In addition, the EEBUS use case requires the unified MMI2 firmware in version 7.8.0 or higher. The leaflet puts it more generally: all units delivered since summer 2023 with the MMI 2 can be used with the HomeHub.
For route 3 the HomeHub reference guide describes the behaviour in more detail than most manufacturers do. Four points matter for planning.
The last point belongs in the conversation with the customer: with route 3 the HomeHub becomes part of the heating system. An unplugged cable or a faulty power supply does not just disable the connection, it stops the heat pump. Both error codes therefore belong in the handover documentation.
There is also a detail that is useful for your own records: the HomeHub keeps an event log that can be downloaded as a CSV file via the local web interface or the ONECTA app. Among other things it contains every accepted and rejected limit and the heat pump's power consumption in the 10 minutes before and after an accepted limit; entries are deleted after 26 months. Why keeping your own records pays off is covered in What curtailment does in practice.
For section 14a, all three routes are sufficient. For subsidising a newly installed heat pump, they no longer are. The directive for the federal funding for efficient buildings – individual measures (BEG EM) of 17 August 2026 states under number 3.4.3:
“Newly installed heat pumps must have a digital interface for grid-oriented control and for connection to a smart metering system including a control device. The digital interface must be interoperable and enable grid-oriented control under section 14a of the Energy Industry Act (EnWG), including the status and feedback information required for it.”
A contact that opens or closes is not a digital interface and provides no feedback. Routes 1 and 2 therefore do not meet the wording. Route 3 is the one Daikin intends for this – the HomeHub reference guide itself says the HomeHub supports “compliance with the local BEG (federal funding for efficient buildings) or section 14a regulations”. Whether a specific installation is subsidised, however, is decided by the funding body, not the manufacturer.
The same number of the directive goes further: from 1 July 2027, the interface of newly installed heat pumps must follow a format in line with the European Commission's Code of Conduct for Energy Smart Appliances, “for example EEBUS in accordance with VDE-AR-E 2829-6”. And anyone receiving the subsidy must, after commissioning, request a smart metering system with control device from the metering point operator if none is installed yet.
For existing installations and heat pumps without subsidy, routes 1 and 2 remain valid. How the three connection routes of a heat pump compare in general is covered in Running a heat pump on electricity prices.
For split, multi-split, Sky Air and VRV units Daikin has a separate leaflet (as of 11 August 2025). The route is the same for all of them: an add-on board that switches the system off via an external contact. For split, multi-split and VRV, Daikin explicitly states an automatic restart as soon as the contact releases again.
| Product group | Board | Note |
|---|---|---|
| Split, multi-split | BRP070A81; BRP070A82 for 2MXM40A9, 2MXM50A9, 2MXM50A8 | one board per outdoor unit; update the outdoor unit's software during commissioning |
| Sky Air | SB.KRP58M51 (RZA-D), SB.KRP58M52 (RZAG-NY/V, RZASG-MY/V), BRP070A81 (RZAG-B) | one board per outdoor unit |
| VRV | DTA104A62-9 | up to 10 outdoor units per board; fitted in the outdoor unit (Maxi VRV) or indoor unit (Mini VRV) |
According to Daikin, only units of the same category are added together, so heat pumps and air conditioners are counted separately. That matches the ruling: room cooling installations are a category of their own there, and the 4.2 kW apply “per category”. More on the threshold in The 4.2 kW in section 14a EnWG.
According to Daikin, yes – every Altherma, at the very least via the utility contact, which switches the unit off during curtailment. Throttling instead of switching off works with the EKRP1AHTA communication board, which is already built into the Altherma 4 and the Altherma GEO. A digital connection via EEBUS runs through the Daikin HomeHub EKRHH.
Not for section 14a alone: the utility contact or the communication board is enough. But if a newly installed heat pump is to be subsidised under the BEG directive of 17 August 2026, the directive requires a digital, interoperable interface with status and feedback information. A relay contact does not provide that; for the Altherma, Daikin intends the HomeHub with EEBUS for this purpose.
That depends on the connection route. Via the utility contact it switches off. With the communication board the auxiliary heater is switched off and the outdoor unit is throttled to a limit set during commissioning. Via the HomeHub with EEBUS, power is limited to the requested value. If the connection between HomeHub and indoor unit drops, the system switches off completely until the connection is restored.
Yes, if the air conditioners behind one grid connection together have a grid connection capacity of more than 4.2 kW. In the Bundesnetzagentur's ruling, room cooling installations form a category of their own. Daikin offers add-on boards for split, Sky Air and VRV units that switch the system off via an external contact.
The manufacturer information comes exclusively from Daikin's own documents, each with its date and the date it was checked. Manufacturer documents change with every firmware release; what counts is the version valid at the time of installation. Quotations from German documents are our translation.
This article reproduces manufacturer information; it replaces neither Daikin's documentation nor the technical connection conditions of your grid operator. Connection and registration are reserved for a registered electrical contractor. Haag Automation has no business relationship with Daikin.
Planning a heat pump and want control, energy management and metering thought through together from the start? Write to me – the initial consultation is free.