Technical article

18 degrees instead of 80: cold district heating

Two networks in the same town, built on opposite logic. One delivers finished heat, the other delivers only the source for it. The difference decides where the heat pump sits, how much insulation is needed – and who carries which risk.

Example
Ilsfeld heat network with the Steinhäldenweg 2 sub-network
Hot network
flow 75–80 °C, return 50–55 °C
Cold network
flow around 18 °C, 35 buildings over 1.2 km
Author
Julian Haag, state-certified electrical engineering technician

The fundamental difference

In a conventional heat network, a central plant produces heat at a usable temperature and distributes it. Whoever is connected receives water hot enough to heat with directly and to make hot water. The transfer station in the basement is essentially a heat exchanger – it transfers heat, it does not generate any.

A cold network turns that around. It distributes water at a temperature you cannot heat with – around 18 °C in this example. Every building has its own heat pump that uses this water as a source and raises it to whatever temperature is actually needed.

Hot and cold network compared In the hot network a central plant produces water at 75 to 80 degrees which insulated pipes carry to the buildings, where only a heat exchanger sits. In the cold network an uninsulated pipe carries water at about 18 degrees to the buildings, and each building has its own heat pump that raises it to heating temperature. Hot network: heat arrives ready to use Heating plant produces 75–80 °C insulated pipe, high temperature losses along the whole route Building: heat exchanger no generation of its own Cold network: only the source arrives Source around 18 °C uninsulated pipe, low temperature hardly any losses, sometimes even a gain from the ground Building: its own heat pump makes the heating temperature The heat pump moves from operator to customer – and with it investment, operation and electricity cost.
Own schematic drawing.

Why a cold network has almost no losses

Heat always flows from warmer to colder, and the faster the greater the difference. A pipe at 80 °C sits in ground at perhaps 10 °C – a gradient of 70 kelvin that the insulation has to work against permanently. That is why a hot network loses heat even when nobody is drawing any.

At a flow temperature of 18 °C the same gradient is only a few kelvin. Losses are so small that insulation hardly pays – a cold network manages with uninsulated plastic pipes. In winter the effect can even reverse: if the ground is warmer than the water, the pipe picks up heat along the way.

This is the decisive advantage, and the reason cold networks work where hot ones fail. In a new development of well-insulated houses, heat demand per plot is small. A hot network there would have poor heat density per metre of route and correspondingly high relative losses. A cold network does not have that problem.

The Ilsfeld twist: fed from the return line

Cold networks usually take their heat from the ground, from groundwater or from waste heat. This example goes a different way, and that is the real point.

The cold network is connected through a heat exchanger to the return line of the hot network. Water comes back from the existing buildings there at 50 to 55 °C – heat the main network no longer uses, but a first-rate source for a heat pump.

The benefit runs both ways. For the new development it is a permanently available, warm source. For the main network: taking heat out of the return lowers its temperature – and a lower return temperature raises the efficiency of the combined heat and power units in the plant. The cold network is therefore not an appendage being supplied along the way; it improves the system it hangs on.

The figures of the example

Hot and cold network in the same supply area
FeatureHot networkCold network Steinhäldenweg 2
Flow temperature75–80 °Caround 18 °C
Return temperature50–55 °C—
Heat sourcewastewater heat pumps, CHP, pellets, biogasreturn line of the hot network
Heat pump locatedin the central plantin every building
Pipe insulationrequirednot required
Sizearound 22.6 km of main route, 421 connections1.2 km, 35 buildings
Heat deliveredaround 10.6 GWh/yraround 392,000 kWh/yr
Primary energy factor0.24 (capped under the Building Energy Act)0.1
Mandatory connectionnonenone

Delivery from the cold network has been remarkably stable over three years: 400,748 kWh in 2022, 393,343 in 2023, 383,122 in 2024 – an average of around 392,000 kWh. No further expansion is planned there.

Why the prices cannot be compared directly

In this example a kilowatt-hour from the cold network costs 6.62 ct excluding VAT, from the hot network 14.19 or 21.07 ct depending on the tariff generation. That looks like a clear advantage, but it is not a comparison of like with like.

With a cold network the customer does not buy finished heat but the source for it. The conversion to heating temperature happens in their own heat pump, and that costs electricity – and before that investment, space and maintenance.

An honest comparison needs three quantities: the network's unit price, your own electricity price and the seasonal performance factor of the heat pump. Roughly: add the electricity price divided by the performance factor to the network price. At a factor of 4 and 30 ct/kWh for electricity that would be about 7.5 ct per kilowatt-hour of heat on top. The numbers are illustrative assumptions – the rule is the point.

Then there is the investment. With a hot network the heat generation sits with the operator, with a cold network with the customer. Anyone assessing an offer should include the heat pump and its installation across its service life – and in return account for the fact that a cold network needs no chimney, no fuel store and no flue inspection.

Which network fits where

The decision practically always comes down to two things: the temperature level the connected buildings need, and the heat density in the area.

Design logic
AreaSuitable networkReason
Older stock, little insulation, radiatorshot networkneeds 70 °C and above; a heat pump in the house would achieve poor performance factors
Dense town centrehot networkhigh heat density per metre of route makes insulation losses relatively small
New development with underfloor heatingcold networklow flow temperatures suffice, heat pumps reach high performance factors
Loose development, small demandcold networka hot network would have excessive relative losses there
Area with cooling demandcold networkthe same network can absorb heat in summer instead of giving it off

The last point is still underrated in Germany: a cold network is bidirectional by nature. Cooling a building in summer means putting the heat into the network, where it benefits somebody else or is stored in the ground. A hot network cannot do that.

What self-builders can take from this

And if the heat pump sits in your own house, recording pays off twice over: source and flow temperature, power draw and heat delivered together give the actual seasonal performance factor. Without it, any economic calculation is guesswork.

Frequently asked questions

What is cold district heating?

A heat network distributing water at a low temperature – around 18 °C in this example. You cannot heat with it directly; every connected building has its own heat pump that uses the water as a source and raises it to the temperature needed.

Why do the pipes of a cold network not need insulation?

Because the temperature difference to the surrounding ground is small. Heat flows away faster the larger that gradient is; at around 18 °C the losses are so small that insulation hardly pays. In winter the pipe may even take up heat from the ground.

Is cold district heating cheaper than a normal heat network?

The unit price is lower, but the prices are not directly comparable. With a cold network you only buy the heat source; the conversion to heating temperature happens in your own heat pump and costs additional electricity. For a comparison, add the electricity price divided by the seasonal performance factor and account for the investment in the heat pump.

Which network suits which area?

Hot networks suit older building stock with high temperature demand and densely built town centres. Cold networks suit new developments with underfloor heating, loose development with low heat demand, and anywhere cooling is also wanted.

Can a cold network provide cooling?

Yes, and that is one of its biggest advantages. Because it works at a low temperature, a building can give heat off to the network in summer instead of drawing from it. A hot network cannot do that.

Sources

Temperature levels, the feed from the return line, delivered volumes and network data come from published documents of the municipality of Ilsfeld. The discussion of design logic and the rule for comparing prices are our own. The source documents are in German.

The worked price comparison uses freely chosen assumptions for electricity price and seasonal performance factor and serves only to illustrate the rule. What binds is the applicable tariff sheet and your contract.

You have a heat pump and want to know its actual seasonal performance factor – measured rather than taken from the datasheet? Send me a message – the first conversation is free.