Heat pump · Dynamic tariff
Running a heat pump on electricity prices
Relay contact, Modbus or the manufacturer's cloud – which route holds up, what funding has required since July 2026, and where control runs into its limits.
Read the article →Technical article · Manufacturers
Bosch and Buderus both belong to Bosch Thermotechnik and solve section 14a the same way: via EEBus, with an internet module on the heat pump. Both brands publish which units master power limitation from which software version – in more detail than most manufacturers. Without EEBus, the SG1 contact input remains, and there newer control panels throttle the heat pump instead of switching it off. This page brings both lists and the control panel instructions together.
From this article on Amazon (Germany):
Bosch Connect-Key K 40 RF* ·
Buderus MX400*
Marked *: affiliate links. As an Amazon Associate I earn from qualifying purchases.
Both brands name the same three prerequisites: an air-to-water or brine-to-water heat pump or a hybrid system, the internet module – the Connect-Key K 40 RF at Bosch, the MX400 LAN and radio module at Buderus – and on the other side an “FNN control unit / hardware on the partner side”. Communication runs over the local network, by cable or Wi-Fi.
The heat pump does not have to hang off an energy manager for this. Buderus writes: “To implement the legal requirements for grid-supportive control under section 14a EnWG, EEBus-capable devices can also communicate directly with the smart meter gateway.” Bosch says the same. An energy management system is the second route, not a prerequisite.
Three EEBus use cases are supported:
Both interfaces pages state, for each unit, from which version of outdoor unit and system controller the EEBus functions are available. Where there is a dash, the manufacturer gives no version.
| Unit | Outdoor unit from | System controller from | Use cases |
|---|---|---|---|
| Logatherm WLW196i AR (S+) | v01.22 | Logamatic BC400, NF 73.06 | LPC, MPC |
| Logatherm WLW186i MB AR, WLW176i MB AR | v07.10 | Logamatic BC400, NF 47.09 | LPC, MPC, OHPCF |
| Logatherm WSW186i | v03.06 | Logamatic BC400, NF 47.09 | LPC, MPC |
| Logatherm WLW166i MBB AR | – | – | LPC, MPC, OHPCF |
| Logatherm WLW186i MBE+ AR | – | – | LPC, MPC, OHPCF |
| Cascade WLW MBE+ mit Logamatic WPM400 K | – | – | LPC, MPC, OHPCF |
| Hybrid package with Buderus hybrid manager | v06.06 | Logamatic HM200.2, NF 47.06, or Logamatic BC400, NF 49.09 | LPC, MPC |
| Unit | Outdoor unit from | System controller from | Use cases |
|---|---|---|---|
| Compress CS 7001i AW, CS 7400i AW | v01.22 | HPC 400, NF 73.06 | LPC, MPC |
| Compress CS 5800i AW, CS 6800i AW | v07.10 | UI 800, NF 47.09 | LPC, MPC, OHPCF |
| Compress CS 7800i LW | v03.06 | UI 800, NF 47.09 | LPC, MPC |
| Compress CS 3400i AW | v02.03 | HPC 400, NF 73.06 | LPC, MPC |
| Compress CS 3800i AW | – | – | LPC, MPC, OHPCF |
| Compress CS 8800i AW | – | – | LPC, MPC, OHPCF |
| Cascade | – | – | LPC, MPC |
| Hybrid package with Bosch hybrid manager | v06.06 | CW 400, NF 47.06, or UI 800, NF 49.09 | LPC, MPC |
The version information is the real value of these lists. A heat pump of the right series whose controller is still on an older version cannot implement the control box's instruction. Check the software version before registration – and record it in the commissioning report.
On its Energy Industry Act page, Buderus names two options: dimming, “e.g. via EEBus”, and “temporary switch-off via the SG interface”. Switching off is enough for section 14a – the ruling lets devices that only know on and off go to the next lower technically possible value. The heat pump then stands still for as long as control lasts.
The control panel instructions have since gone further. At the SG1 contact input – the “External input 1” menu – newer software versions offer throttling as well as blocking. Bosch (UI 800 control panel) and Buderus (Logamatic BC400 and BC400-FO) describe it in the same words: “throttling of compressor and auxiliary heater under section 14a EnWG Germany”. Whether a unit can do it is decided mainly by the control panel's software:
| Software | Choice at external input 1 | Power during curtailment according to the control panel instructions |
|---|---|---|
| NF47 up to NF47.11 | utility block time only | off |
| NF47.12 (air-to-water, instructions 2025/06) | “EVU Sperrung 1” (block) or “EVU-Sperre 4” (throttling) | no value given |
| NF87.01 and NF87.02 (instructions from 2025/09) | “EVU Sperrung 1” or “EVU Dimmen” (dimming) | no value given |
| NF87.03 and NF87.04 (instructions from 2026/08) | “EVU Sperrung 1” or “EVU Dimmen” | “4.2 kW or 40 % of the maximum heat output of compressors and auxiliary heaters” |
According to the tables above, the Compress CS 5800i and CS 6800i AW and the Logatherm WLW176i and WLW186i MB AR run with a control panel of the NF47 line; for them it depends on whether the control panel is already on NF47.12. How the throttling is wired is described in identical terms in the instructions for the new indoor units Compress AWEi and AWEiD (for the outdoor units CS 3800i, CS 5801i and CS 8800i AW) and Logatherm WLW176i.2 E and WLW186i.2 E:
One point does not match the ruling. From the 2026/08 edition, the footnote limits power consumption “to 4.2 kW or 40 % of the maximum heat output”. The ruling applies the factor 0.4 to the electrical grid connection capacity, and only for heat pumps above 11 kW; below that, 4.2 kW applies (Annex 1, clause 4.5.1). The auxiliary heater counts towards it (clause 2.4.1 b); that Bosch and Buderus limit compressor and auxiliary heater together fits this. None of the instructions names a value that can be set, unlike Viessmann. Which limit the unit actually applies above 11 kW cannot be read from the documents. For such systems, the question belongs with the manufacturer before registration. The calculation itself: The 4.2 kW in section 14a EnWG.
The software version is shown in the service menu under “Info > System components”. It belongs in the commissioning report, together with the option set at external input 1.
Be careful with example figures on manufacturer pages: the same Buderus page states €161 a year (module 1) and 4.33 ct/kWh (module 2) for Netze BW. Netze BW's 2026 price sheet shows €147.56 and 3.61 ct/kWh. Grid fees change every year; what counts is your own grid operator's price sheet.
For section 14a, any route the manufacturer names is enough. For subsidising a newly installed heat pump it is not: under number 3.4.3, the BEG EM directive of 17 August 2026 requires a “digital interface for grid-oriented control” that is “interoperable” and enables control under section 14a “including the status and feedback information required for it”. A contact that opens or closes provides no feedback – not even if the heat pump then throttles instead of switching off. From 1 July 2027, the interface of newly installed heat pumps must also follow a format in line with the Code of Conduct for Energy Smart Appliances, “for example EEBUS in accordance with VDE-AR-E 2829-6”.
This applies to funding applications from 21 July 2026. Older applications remain under the version of 21 December 2023, where an interface such as SG Ready is enough. Neither version requires the grid operator's control box to be installed: KfW heat pump subsidy when the control box is still missing.
Whether a specific installation is subsidised is decided by the funding body, not the manufacturer. The connection routes compared: Running a heat pump on electricity prices.
For the units both brands list on their interfaces pages, yes: via EEBus they support power limitation (LPC) and power monitoring (MPC). The prerequisites are an internet module – the MX400 LAN and radio module at Buderus, the Connect-Key K 40 RF at Bosch – and the software version of outdoor unit and system controller stated there.
For the EEBus connection, yes – the module provides the interface. Without the module, the SG1 contact input remains, through which the heat pump switches off or throttles, depending on the control panel software. But if a newly installed heat pump is to be subsidised under the BEG directive of 17 August 2026, the directive requires a digital interface with feedback information; of the two routes, that is the EEBus one.
Via the SG1 contact input, if the control panel is recent enough. The instructions for the Bosch UI 800 and Buderus BC400 offer throttling of compressor and auxiliary heater under section 14a at external input 1: in the NF47 software line from NF47.12 as “EVU-Sperre 4”, in the NF87 line as “EVU Dimmen”. Older software versions only know switching off. The service menu shows the installed software under Info > System components.
Yes. Both brands state that EEBus-capable units can also communicate directly with the smart meter gateway to implement section 14a. An energy management system is possible but not a prerequisite.
The manufacturer information comes exclusively from the manufacturer's own documents, each with its date and the date it was checked. Manufacturer documents change with every firmware release; what counts is the version valid at the time of installation. Quotations from German documents are our translation.
This article reproduces manufacturer information; it replaces neither Bosch and Buderus's documentation nor the technical connection conditions of your grid operator. Connection and registration are reserved for a registered electrical contractor. Haag Automation has no business relationship with Bosch and Buderus.
Links marked with an asterisk are affiliate links. As an Amazon Associate I earn from qualifying purchases; the price is unchanged for you. What I recommend does not depend on it.